Fire and heat protection
General:
Mounted surfaces made of or containing combustible materials (components to be protected) must be insulated or
shielded, so no temperatures can occur on these that exceed values greater than 85 °C. The same applies to built-in
furniture. The building requirements of the respective state building regulations and state ordinances (e.g. fire code
ordinance, guideline of the Austrian institute of construction engineering
“OIB”, …) must be adhered to.
In the event that ELECTRICAL INSTALLATIONS and/or ELECTRICAL COMPONENTS are present in/on the mounting wall,
then the fire protection must be implemented as follows:
Electrical installations and/or electrical components on the side facing the stove
Construction of the
insulation just as the mounting surfaces TO BE PROTECTED.
Electrical installations and/or electrical components on the rear of the mounting wall, wall thickness greater
than 12.5 cm and mounting wall detached at the rear
Construction of the installation just like with
mounting surfaces NOT TO BE PROTECTED.
Mounting surfaces TO BE PROTECTED
10 cm brick 10 cm insulation (in accordance with AGI Q132).
In the event of the use of Ortner Isoboard: 10 cm brick 9 cm Ortner Isoboard.
Or 3 cm Isoboard at the mounting wall + active back ventilation (at least 5 cm gap width) + 6 cm Ortner Isoboard
(towards the stove, with offset joints).
Mounting surfaces NOT TO BE PROTECTED
8 cm insulation (in accordance with AGI Q132).
In the event of the use of Ortner Isoboard: 6 cm Ortner Isoboard.