23
Recessed Ledge Detail
A ledge over the top of a fireplace that is less than 24 inches from the top of the fireplace viewing area must maintain a minimum
of
12 inches from the top of the viewing area to the top of the framing
.
Entire structure must be non-combustible
(framing and finish).
Ledge Size: A x B ≤
340 sq. in.
A = ledge depth, B= ledge width (Top View)
Oversized Ledge
If ledge surface area exceeds 340 sq. in., the heat release must be divided between the ledge and the chase ceiling: 25% at
the ledge and 75% at the chase ceiling.
NOTE: Chase area minimum requirements must be met throughout the entire fireplace chase. See “Chase Area
Minimum” section above for details.
Oversized Ledge