10.1. Connecting a waste oil tank 23132 (2-Levels)
To achieve a proper function, that is the pump stops if the physical tank is full or if the sensor is disconnected, the
following connection should be made.
The TSM port should be set to control the appropriate PC tank in relation to the physical tank.
Correct TankType, TSMAddress and TSMPort should be set using with WinDB Manager
MASK = 13, TankType = 11?.
11. To connect an analogue sensor
The four analogue inputs on the TSM support any standard industrial 2-lead / 4-20mA / 24VDC sensors. To connect
sensors a 2-pole connector is used.
11.1. Analogue sensor 23417
The submerged pressure based level sensor 23
417 is a robust sensor that can be used with good
accuracy for tanks with a height of 1 – 5 meters.
Max height depends on density of fluid. The
measuring resolution for a TSM with a 23 417
sensor is 4 mm for water and about 4.5 mm for
mineral oil.
Connect the red wire to +24VDC and the black
wire to Sense. +24VDC and Sense are printed on
the PCB.
If the sensor cable (6.5 m) is to short to reach the
TSM it can be lengthen using a standard 2-lead
wire with copper area of 0.5 mm2 for each lead.
For this purpose use the by-packed connection
box.
It is not necessary to use the shield to obtain a good signal because the signal is current based. The shield can be
used for protection grounding purposes if needed.
OBSERVE! It is important that the transparent tube is not blocked and that the humidity protection filter is
used. A blocked tube will cause measuring failure. Not using the humidity protection could
cause sensor malfunction due to corrosion caused by condensed water.