9. To connect discrete level sensors 23 132/138/171 and solenoid valves
9.1. Fresh oil tank, 23138 (2-levels)
To achieve a proper function, that is the pump starts only if there are enough oil in the tank, a dispense point is open
and the sensor works properly, the following connection should be made.
The TSM port should be set to control the appropriate PC tank in relation to the physical tank. Correct TankType,
TSMAddress and TSMPort should be set using with WinDB Manager.
MASK =12, TankType = 01?
9.2. Fresh oil tank, 23171/23183 (1-level)
To achieve a proper function, that is the pump starts only if there are enough oil in the tank, a dispense point is open
and the sensor works properly, the following connection should be made.
The TSM port should be set to control the appropriate PC tank in relation to the physical tank. Correct TankType,
TSMAddress and TSMPort should be set using with WinDB Manager.
Mask = 4, TankType=01?
9.3. Waste oil tank, 23132 (2-levels)
To achieve a proper function, that is the pump stops if the physical tank is full or if the sensor is disconnected, the
following connection should be made. Colours are if you use control cable 23412.
The TSM port should be set to control the appropriate PC tank in relation to the physical tank. Correct TankType,
TSMAddress and TSMPort should be set using with WinDB Manager
MASK = 13, TankType = 11?
Solenoid valve
TCM
23138
LOW
HIGH
1 C
2 NO
3 NC
4 C
5 NO
6 NC
+24 V
A
GND
B
Sol
Solenoid valve
TCM
Blue
Brown
23171
+24 V
A
GND
B
Sol