Ball screw lead: 12 mm 

Setting example 

Initial value

 

Setting items 

Setting value 

Converted 

value 

Setting value 

Converted 

value 

Ball screw lead [mm] 

12 

 12 

 

Resolution  
(Minimum travel amount [mm]) 

1200 (0.01) 

 1000 

(0.012) 

 

Electronic gear A 

 

 

Electronic gear B 

 

 

Coordination 

Motor rotation direction 

Positive direction=CW 

(The linear slide table 

moves to opposite the 

motor side) 

 

Positive direction=CW 

(The linear slide table 

moves to opposite the 

motor side) 

 

Position [step] 

1000 

10 [mm] 

0 0 

[mm] 

Operating speed [Hz] 

10000 

100 [mm/s]

1000 12 

[mm/s] 

Operation 
data 

Acceleration (deceleration) rate 
[ms/kHz] 
(Setting value1: 0.001 ms/kHz) 

1000 

10 [m/s

2

]

1000 12 

[m/s

2

JOG operating speed [Hz] 

10000 

100 [mm/s]

1000 12 

[mm/s] 

JOG acceleration (deceleration) 
rate [ms/kHz] 
(Setting value1: 0.001 ms/kHz) 

1000 

10 [m/s

2

]

1000 12 

[m/s

2

Operation 

JOG starting speed [Hz] 

600 

6 [mm/s]

500 6 

[mm/s] 

Home-seeking mode 

Push mode 

 

3-sensor mode 

 

Starting speed of home-seeking 
[Hz] 

600 

6 [mm/s]

500 6 

[mm/s] 

EAS4 

0 [mm] 

0 0 

[mm] 

Position offset of 
home-seeking [step] 

EAS6 

300 

3 [mm] 

0 0 

[mm] 

Return-to- 
home 

Starting direction of 
home-seeking 

Negative direction 

(Return-to-home  

operation starts to the 

motor side) 

 

Positive direction 

(Return-to-home 

operation starts to 

opposite the motor side) 

 

Positive software limit [step] 

(Stroke × 100) + 300 

[mm] 

8388607 

100663.284 

[mm] 

Coordination 

Negative software limit [step] 

200 

2 [mm] 

8388608 

100663.296 

[mm] 

∗ 

Factory setting data or initialized data.

 

 

Note 

• 

When performing sensorless return-to-home operation upward in a vertical direction with the 

EAS4

 type, keep the 

load mass to be less than 4 kg. 
If the load mass is 4 kg or more, the actuator cannot push up to the position of the mechanical stopper, causing 
variation in the stopping accuracy of return-to-home. 

• 

Set the value of the "position offset of home-seeking" to be the following value or larger. If sensorless 
return-to-home operation is performed keeping the initial values, the linear slide table becomes a state of contacting 
the dedicated stop buffer, causing a negative effect on the stopping accuracy of return-to-home. 
 

EAS4

: 2 mm (setting value: 0, moves 200 steps from the actuator end) 

 

EAS6

: 5 mm (setting value: 300, moves 500 steps from the actuator end) 

• 

Conversion formula 

 

Lead [mm]

1000 × (Electronic gear B / Electronic gear A )

Minimum step angle [mm] =

Acceleration/deceleration speed [m/s

2

]

=

Speed [mm/s]

2

3

4

㪪㫇㪼㪼㪻㩷

[Hz]

× Minimum travel amount [mm]

㪤㫀㫅㫀㫄㫌㫄㩷㫋㫉㪸㫍㪼㫃㩷㪸㫄㫆㫌㫅㫋㩷

[mm]

× 1000 × 1000

Acceleration and deceleration rate [ms/kHz

Position [mm]

1

= Position [step]

× Minimum travel amount [mm]

Starting direction of home-seeking [mm]

= Starting direction of home-seeking [step] × Minimum travel amount [mm]

 

 

∗1 

Set the position within the stroke range of the actuator. 

∗2 

Set the operating speed by checking the specification of the maximum speed for each actuator. 

∗3 

Set the operating speed of JOG operation for test operation to 250 mm/sec or less. 

∗4 

Set the starting speed to 6 mm/sec or less. 

∗5 

Set the acceleration/deceleration speed by checking the specification of the maximum acceleration/deceleration speed for each actuator. 

 

Summary of Contents for LSD-KD

Page 1: ...C3 EN 55011 group 1 class A EMS Immunity Tests Radiation Field Immunity Test Electrostatic Discharge Immunity Test Fast Transient Burst Immunity Test Conductive Noise Immunity Test EN 61000 6 2 EN 618...

Page 2: ...W1 CN3 CN2 CN1 CN4 POWER ALARM LED C DAT C ERR LED CN9 CN8 CN5 DIN RS 485 CN6 CN7 SW3 POWER ALARM LED POWER ALARM C DAT C ERR LED C DAT RS 485 C ERR RS 485 SW1 RS 485 SW3 No 1 RS 485 0 SW2 RS 485 RS 4...

Page 3: ...100 mm 2 IP54 50 C DIN DIN DIN DIN DIN DIN DIN 10 20 N DIN DC24 V 5 GND FG DC24 V GND 2 1 CN9 CN6 CN7 RS 485 CN8 CN5 CN3 OPX 2A MEXE02 CN2 CN1 1 FG AWG24 16 0 2 1 25 mm2 2 AWG26 20 0 14 0 5 mm2 RS 48...

Page 4: ...5 No 1 LS 2 LS 3 HOMES 4 SLIT 5 IN COM2 1 2 3 4 5 CN8 No 1 IN0 0 HOME 2 IN1 1 START 3 IN2 2 M0 4 IN3 3 M1 5 IN4 4 M2 6 IN5 5 FREE 7 IN6 6 STOP 8 IN7 7 ALM RST 9 IN COM1 1 2 3 4 5 6 8 9 7 CN9 No 1 OUT0...

Page 5: ...FF SW3 No 1 ON 0 0 16 1 1 17 2 2 18 3 3 19 4 4 20 5 5 21 6 6 22 7 7 23 8 8 24 9 9 25 A 10 26 B 11 27 C 12 28 D 13 29 E 14 30 F 15 31 Modbus 0 SW2 7 SW2 bps SW2 bps 0 9600 4 115 200 1 19200 5 6 2 38400...

Page 6: ...step 1000 10 mm 0 0 mm Hz 10000 100 mm s 1000 6 mm s ms kHz 1 0 001 ms kHz 1000 10 m s 2 1000 6 m s 2 JOG Hz 10000 100 mm s 1000 6 mm s JOG ms kHz 1 0 001 ms kHz 1000 10 m s 2 1000 6 m s 2 JOG Hz 600...

Page 7: ...G ms kHz 1 0 001 ms kHz 1000 10 m s 2 1000 12 m s 2 JOG Hz 600 6 mm s 500 6 mm s 3 Hz 600 6 mm s 500 6 mm s EAS4 0 0 mm 0 0 mm step EAS6 300 3 mm 0 0 mm step 100 300 3 mm 8388607 100663 284 mm step 20...

Page 8: ...t ORIENTAL MOTOR CO LTD 2012 http www orientalmotor co jp TEL 0120 911 271 9 00 18 30 TEL 0120 925 410 FAX 0120 925 601 TEL 0120 925 420 FAX 0120 925 602 TEL 0120 925 430 FAX 0120 925 603 8 00 20 00 9...

Page 9: ...VDC it is not subject to the Low Voltage Directive but install and connect this product as follows This product is designed and manufactured to be installed within another device Install the product...

Page 10: ...Series Model Actuator model Driver model EAS4 KD EASM4 K EAS4 M KD EASM4 MK EAS6 KD EASM6 K EAS6 M KD EASM6 MK LSD KD Names and functions of parts Transmission rate setting switch SW2 Address number s...

Page 11: ...Area free of radioactive materials magnetic fields or vacuum 1000 m 3300 ft or lower above sea level Installation method Mount the driver to a 35 mm 1 38 in width DIN rail When installing two or more...

Page 12: ...ata edit connector CN3 and RS 485 communication connectors CN6 CN7 of the driver are not electrically insulated When grounding the positive terminal of the power supply do not connect any equipment PC...

Page 13: ...2 38400 7 Network converter 3 57600 8 F Not used Note Do not set SW2 to positions 5 6 and 8 to F Termination resistor Turn the SW3 No 4 of the termination resistor setting switch ON to set the termina...

Page 14: ...lue Setting value Converted value Ball screw lead mm 6 6 Resolution Minimum travel amount mm 600 0 01 1000 0 006 Electronic gear A 5 1 Electronic gear B 3 1 Coordination Motor rotation direction Posit...

Page 15: ...or initialized data Note When performing sensorless return to home operation upward in a vertical direction with the EAS4 type keep the load mass to be less than 4 kg If the load mass is 4 kg or more...

Page 16: ...other countries Copyright ORIENTAL MOTOR CO LTD 2012 Please contact your nearest Oriental Motor office for further information Technical Support Tel 800 468 3982 8 30 A M to 5 00 P M P S T M F 7 30 A...

Reviews: