http://www.hicoolopticlimate.com/
3
Note:
Nominal cooling conditions: indoor dry bulb temperature is 27
℃
, indoor wet bulb temperature is 19
℃
,
outdoor dry bulb temperature is 35
℃
, outdoor wet bulb temperature is 24
℃
.
Note:
1) When the unit is shipped from the factory, the refrigerant R417A has been
discharged from the unit;
2) After the unit is installed, the indoor and outdoor unit connecting pipes are
connected and leak tested, open the valve to vacuum, and fill the refrigerant
according to the nameplate refrigerant quantity (connecting pipe is 3 meters);
3) When the connecting pipe exceeds 3 meters, additional refrigerant should
be added:
Liquid pipe Φ9.52 is 52g/m
(
Elite 6000/10500 Split
)
Liquid pipe Φ12.7 is 110g/m
(
Elite 15000 Split
)
4
)
When the unit needs to replenish the refrigerant quantity, it is necessary to
disassemble the maintenance board and replenish the refrigerant from the low
pressure needle valve.