11
V - Systems Owner’s Manual O.A.S. 2010
c
VII. V - Systems Electrical Data
I
O
Customer supplied
receptacle fed from 2
pole dedicated circuit
breaker.
6 - 20R
6 - 20P
Magnetic Starter -
Mount close to
collector
6’ long type SJT 14 AWG
power cord
Motor
Note: This dust collector is
pre-wired at the factory and
need only be plugged into
a dedicated NEMA 6-20R
electrical receptacle. 2 & 3hp
single phase V-Systems only.
Always Use A Licensed, Professional Electrician.
What size circuit breaker for the V-2000?
What size circuit breaker for the V-1500?
The circuit breaker OAS recommends is a 2 pole ‘HACR’ style (or equivalent) 15 amp rated for
250 volts AC.
The circuit breaker OAS recommends is a 1 pole ‘HACR’ style (or equivalent) 20 amp rated for
120 volts AC.
What size circuit breaker for the V-3000?
What size circuit breaker for the V-5000?
The circuit breaker OAS recommends is a 2 pole ‘HACR’ style (or equivalent) 20 amp rated for
250 volts AC.
The circuit breaker OAS recommends is a 2 pole ‘HACR’ style (or equivalent) 30 amp rated for
250 volts AC.
“HACR’ style breakers are required because they are designed to accommodate high amperage inrush (prevents nui-
sance tripping of the circuit breaker when the dust collector motor starts). Make sure that the conductor(s) used to ‘feed’
the NEMA 6-20R dedicated receptacle are sized per NEC (NEC = National Electrical Code) Article 310 entitled ‘Conduc-
tors for General Wiring’. Always use a licensed professional electrician to install the electrical circuit between the circuit
breaker panel, and the NEMA 6-20R dedicated receptacle that is used to power up the factory installed magnetic starter
that comes on the V-2000 or the V-3000.
Wall mounting
Magnetic Starter.
Fastener
Captive Fastener
Remove front cover.
Attach Starter cover and tighten
Captive Fasteners.
Fasten screws through mount-
ing bracket into mounting
surface. (Screw needs to be
smaller than Captive Fastener.)