Long-life Two-circuit Limit Switch

 

WLM

@

F-107

Lim

it 

Switch

es

Precautions

Correct Use

When wiring terminal screws, use M4 round crimp terminals and
tighten screws to the recommended torque. Wiring with broken
wires, or the incorrect crimp terminals, or not tightening screws to the
recommended torque can lead to short-circuits, leakage current, and
fire.

When performing internal wiring there is a chance of short-circuit,
leakage current, or fire, so be sure to protect the inside of the Switch
from splashes of oil or water, corrosive gases, and cutting powder.

Using an inappropriate connector or assembling Switches incorrectly
(assembly, tightening torque) can result in malfunction, leakage cur-
rent, or fire, so be sure to read the instruction manual thoroughly
beforehand.

Even when the connector is assembled and set correctly, the end of
the cable and the inside of the Switch may come in contact. This can
lead to malfunction, leakage current, or fire, so be sure to protect the
end of the cable from splashes of oil or water and corrosive gases.

Environmental Precautions

When the Switch is used in locations subject to splashes of water or
oil, the material of the seal, which ensures the sealing properties of
the Switch, may undergo changes in shape and quality. This is due to
deterioration (including expansion and contraction), and may result in
reduced performance, ineffective return, and ineffective sealing
(leading to ineffective contact, insulation, leakage current, and fire).
Confirm the possible effects of the operating environment on the
Switch before use.

Built-in Switch

Do not replace the built-in switch. If the position of the insulation
sheet moves (separator), the insulation may become ineffective.

Tightening Torque

If screws are too loose they can lead to an early malfunction of the
Switch, so ensure that all screws are tightened using the correct
torque.

In particular, when changing the direction of the Head, make sure
that all screws are tightened again to the correct torque. Do not allow
foreign objects to fall into the Switch.

Installing the Switch

To install the Switch, make a mounting panel, as shown in the follow-
ing diagram, and tighten screws using the correct torque.

Connectors

Either the easy-to-use Allen-head nut or the SC Connector can be
used as connectors. To ensure high-sealing properties, use the SC
Connector. (SC-1M to -5M and others.)

No.

Type

Torque

1

Head mounting screw

0.78 to 0.88 N·m

2

Cover mounting screw

1.18 to 1.37 N·m

3

Allen-head bolt 
(for securing the lever)

4.90 to 5.88 N·m

4

Terminal screw

0.59 to 0.78 N·m

5

Connector

1.77 to 2.16 N·m

6

Main Unit screws

4.90 to 5.88 N·m

0

Four, 5.2

+0.2 

dia. mounting holes or M5 taps

Summary of Contents for WLM -

Page 1: ...ibility when setting stroke zones Model Number Structure Model Number Legend 1 Actuators CA2 Roller lever Standard GCA2 Roller lever High precision H2 Roller lever Overtravel general purpose G2 Roller lever Overtravel high sensitivity 2 Wiring Specifications Blank Screw terminal G1 2 conduit K13A Direct wired connector 2 core AC K13 Direct wired connector 2 core DC K43A Direct wired connector 4 co...

Page 2: ...possible Head can be mounted in any of the four directions See note 3 One side operation possible Head can be mounted in any of the four directions See note 3 Screw terminal WLMCA2 LD WLMH2 LD WLMG2 LD WLMGCA2 LD Direct wired connector 2 core AC WLMCA2 LDK13A WLMH2 LDK13A WLMG2 LDK13A WLMGCA2 LDK13A DC WLMCA2 LDK13 WLMH2 LDK13 WLMG2 LDK13 WLMGCA2 LDK13 4 core AC WLMCA2 LDK43A WLMH2 LDK43A WLMG2 LD...

Page 3: ...ty 115 VAC 5 115 VDC 0 4 Inrush current NC 30 A max 15 A max See note NO 20 A max 10 A max See note Model Rated voltage Non inductive load Inductive load Resistive load Lamp load Inductive load Motor load NC NO NC NO NC NO NC NO DC 12 VDC 3 3 3 3 3 3 3 3 24 VDC 3 3 3 3 3 3 3 3 48 VDC 3 3 3 3 3 3 3 3 115 VDC 0 8 0 8 0 2 0 2 0 8 0 8 0 2 0 2 AC 115 VAC 3 3 3 1 5 3 3 3 2 5 Degree of protection IP67 Du...

Page 4: ...d down Operating characteristics WLMCA2 LD Standard models WLMH2 LD Overtravel models general purpose WLMG2 LD Overtravel models high sensitivity WLMGCA2 LD High precision models OF max 9 81 N 9 81 N 9 81 N 13 34 N RF min 0 98 N 0 98 N 0 98 N 1 47 N PT OT min 30 55 65 40 MD max 12 12 7 3 15 5 15 5 10 2 1 5 2 0 Lamp equipped Light ON when not operating Internal circuit Built in switch Lamp equipped...

Page 5: ... that the load turns ON when the actuator is free When the indicator lamp is set to light ON when not operating con nect the load on the NO side and set so that the load turns ON when the actuator is pushed down Light ON when Operating When the Switch s contacts and the internal circuit of the lamp holder are connected in parallel there is large resistance from the internal circuit so the current ...

Page 6: ...h with SPST NO NC contact form Bearing The bearing smooths the plunger movement Shaft Section Seal By fitting a double seal consisting of an oil seal and an X ring to the rotary shaft even greater sealing properties are achieved Head The Head can be mounted in any of the four directions by removing the screws at the four corners of the Head Requires maintenance excessive overtravel Proper range Re...

Page 7: ... 12 Allen head bolt Rubber cap Three M4 13 Lamp cover JIS B0202 G1 2 Effective thread 4 threads min Four M6 Depth 15 min 60 max Four 5 2 0 2 dia holes 0 17 5 dia 5 See note Four M3 5 length 26 5 M5 12 Allen head bolt Rubber cap Three M4 13 Lamp cover JIS B0202 G1 2 Effective thread 4 threads min 0 Four 5 2 0 2 dia holes Four M6 Depth 15 min 60 max 42 max SC 2FD M12 1 Note Stainless steel roller No...

Page 8: ...re to change the plunger for internal opera tions at the same time The operational plunger does not need to be changed on overtravel general purpose and overtravel high sensitivity models Roller Levers WLMCA2 WLMH2 WLMG2 WLMGCA2 Changing the operating direction By removing the Head on models which can operate on one side and then changing the direction of the operation al plunger one of three oper...

Page 9: ... changes in shape and quality This is due to deterioration including expansion and contraction and may result in reduced performance ineffective return and ineffective sealing leading to ineffective contact insulation leakage current and fire Confirm the possible effects of the operating environment on the Switch before use Built in Switch Do not replace the built in switch If the position of the ...

Page 10: ...n the shaft section can be seen Terminal Plate By using a short circuit plate as shown in the following diagram the Switch can be fabricated into a single polarity double break model When ordering specify WL Terminal Plate IWPA01 D dia dz dia dz dia 4 3 D dia 4 5 B 8 5 L 21 0 F 7 8 l 9 0 mm Ground terminal NO terminal NC terminal 16 0 15 9 0 2 2 1R 2R 3R t 0 6 Copper plate In the interest of produ...

Reviews: