background image

13

F3SJ-B-02TS

Quick Installation Manual

When muting function is used, muting state can be checked from where a worker operates or adjust the 

machine.

Neither connector nor bracket must be loose.

-Checking that Hazardous Parts Stop While the Machine Operates

The hazardous parts are movable when nothing is in the detection zone.

The hazardous parts stop immediately when a test rod is inserted into the detection zone at three posi-

tions: "directly in front of the emitter", "directly in front of the receiver", and "between the emitter and 
receiver". (Use the appropriate test rod.)

The hazardous parts remain stopped as long as the test rod is in the detection zone.

The hazardous parts stop when the power of the F3SJ-B-02TS is turned OFF while nothing is in the 

detection zone.

-Items to Inspect Every 6 Months or When Machine Settings Are Changed

In addition to inspection item at operation start, following items must also be verified.

The outputs of the F3SJ-B-02TS and the machine are properly wired.

The total number of times that the control relays/contactors have switched is significantly lower than their 

design lives.

There is no disturbance light.

When F3SJ-B-02TS is connected again, a secondary sensor farthest from its power supply has either of 

the followings:
• Cap
• Key cap for muting

Power supply's 0 V must be grounded.

Wiring must not be bent, cracked, nor damaged.

 

Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the 
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable 
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by 
itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, 
machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the 
particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all 
cases. 
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT 
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE 
OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL 
EQUIPMENT OR SYSTEM.
See also Product catalog for Warranty and Limitation of Liability.

Suitability for Use

In the interest of product improvement, specifications are subject to change without notice.

Regional Headquarters

OMRON EUROPE B.V. (Representative and Importer in EU)
Wegalaan 67-69, NL-2132 JD Hoofddorp
THE NETHERLANDS
Tel: (31)-2356-81-300 / FAX: (31)-2356-81-388

OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200 
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011 / Fax: (65) 6835-2711

OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222 / Fax: (86) 21-5037-2200

OMRON Corporation

Industrial Automation Company (Manufacturer)

Contact: www.ia.omron.com

Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN

Suitability for Use

/Contact Information

Mounting/Beam Alignment

Wiring

Function Selection

Pre-Operation Checklist /

Maintenance Checklists

Summary of Contents for Sti F3SJ-B P25-02TS Series

Page 1: ...urtain F3SJ B P25 02TS Series OMRON Corporation 2017 2018 All Rights Reserved Original instructions Quick Installation Manual Relevant manual Cat No Safty Light Curtain F3SJ B 02TS User s Manual SCHG...

Page 2: ...attach the top bottom brackets F39 LJB1 and intermediate brackets F39 LJB2 6 6 5 Mounting and Beam Alignment 8 7 Pre Operation Checklists Maintenance Checklists 11 Suitability for Use Contact Informa...

Page 3: ...Green 1 Top beam state indicator Blue 10 Bottom beam state indicator Blue 9 External device monitoring indicator Green 8 Not used 7 Internal error indicator Red 6 Configuration indicator Green 5 Comm...

Page 4: ...Use the following flow chart to determine the system For configuration to use the muting function refer to F3SJ B 02TS series user s manual Using Muting Function Basic System Muting System 1 NO YES 1...

Page 5: ...itter Receiver Gray Communication line Pink Communication line Power supply 24 VDC F39 JD A L F39 JD A D 1 1 2 1 Use a switch for micro loads Input specifications 24V 1 0mA or less 2 F3SJ can work eve...

Page 6: ...e through the setting tool see Step 3 3 Reducing operating range setting change by the setting tool is required 4 Keep sufficient distance between the F3SJ B 02TSs so that mutual interference does not...

Page 7: ...brackets as many as and on the positions specified in the dimensional drawing Otherwise ratings specifications cannot be satisfied If load is applied to the sensor unit in your environment add interm...

Page 8: ...ad is applied to the sensor unit in your environment add intermediate bracket s For mounting brackets other than top bottom brackets F39 LJB1 and intermediate brackets F39 LJB2 as well as external dim...

Page 9: ...Intermediate Bracket 2 Intermediate Bracket 3 Intermediate Bracket 1 Loosen Intermediate Bracket 2 Attach the intermediate mounting bracket 2 to 3 Intermediate Bracket 3 Side mounting Hexagon socket h...

Page 10: ...Loosen Wall mounting screw M5 Wall mounting screw M5 Wall mounting screw M5 Wall mounting screw M5 Wall mounting screw M5 Wall mounting screw M5 Tighten securely Hexagon socket head cap screw M3 x 12...

Page 11: ...to the center of the angle where stable indicator STB turns ON Emitter Receiver TOP indicator Blue STB indicator Green BTM indicator Blue RECEIVER EMITTER On when light intensity is 170 or higher of...

Page 12: ...ing state can be checked from where a worker operates or adjust the machine A muting sensor consists of two independent devices Not used in flammable or explosive atmosphere Wiring Check Before Power...

Page 13: ...than the calculated value Maintenance Checklists To ensure safety keep a record of the inspection results When the user is a different person from those who installed or designed the system he she mu...

Page 14: ...ty certification documents identifying ratings and limitations of use which apply to the Product This information by itself is not sufficient for a complete determination of the suitability of the Pro...

Page 15: ...F3SJ B P25 02TS OMRON Corporation 2017 2018 All Rights Reserved Original instructions...

Page 16: ...02TS F3SJ B 02TS F3SJ B 02TS http www fa omron co jp 1 1 2 2 3 2 4 3 5 4 5 1 EDM PNP 4 5 2 EDM PNP 4 6 5 6 1 F39 LJB1 F39 LJB2 5 6 2 7 7 10 10 1 LED F3SJ B 02TS F3SJ B P25 02TS 1 1 F3SJ B 02TS 3 1 1...

Page 17: ...2 F3SJ B 02TS 2 3 3 4 5 10...

Page 18: ...3 F3SJ B 02TS 4 F3SJ B 02TS...

Page 19: ...4 F3SJ B 02TS 5 F3SJ B 02TS 5 1 EDM PNP 5 2 EDM PNP 1 24V 1 0mA 2 K1 F3SJ 1 24V 1 0mA 2 K1 F3SJ...

Page 20: ...SJ B 02TS 6 F39 LJB1 F39 LJB2 F3SJ B 02TS 6 1 F39 LJB1 F39 LJB2 0 0 0 0 0 0 0 0 3 mm 545mm A E P E E E 530mm A C 69 B C 42 2 C 4 D C 45 E P 20 E 0225 0545 0 0625 1105 1 B 2 1185 1585 2 B 3 1665 1985 3...

Page 21: ...6 F3SJ B 02TS 0 0 0 0 0 0 0 0 mm 545mm F39 LJB1 F39 LJB2 F3SJ B 02TS A E E E E 700mm A C 69 B C 42 2 C 4 D C 45 E E 0225 0545 0 0625 1105 1 B 2 1185 1585 2 B 3 1665 1985 3 B 4...

Page 22: ...7 F3SJ B 02TS 6 2 1 2 6 1...

Page 23: ...8 F3SJ B 02TS 3 4...

Page 24: ...9 F3SJ B 02TS 5 F39 LJB2 30 6 M3 8 M3 18 1 EMITTER RECEIVER...

Page 25: ...10 F3SJ B 02TS 7 F3SJ B 02TS F3SJ B 02TS F3SJ B 02TS Web 0120 919 066 8 00 21 00 365 FAX Web PHS IP 055 982 5015 FAX 055 982 5051 www fa omron co jp a b 24 c d a d...

Reviews: