Depending on the application or the result of the risk assessment according to EN ISO 13849-1, the device must be wired as 

shown in Fig. 1 to Fig. 11. Non-time delayed contacts can be used up to category 4, PL e, time-delayed safety contacts up to 

category 3, PL e. 

Applications 

Fig. 3: 

Single-channel emer-

gency stop circuit with 

earth fault monitoring. 
(category 1, up to PL c) 

Fig. 2: 

Two-channel emergen-

cy stop circuit with earth 

fault monitoring. 
(category 3, up to PL d) 

Fig. 1: 

Two-channel emergen-

cy stop circuit with 

short circuit and earth 

fault monitoring. 
(category 4, up to PL e) 

Fig. 4: 

Two-channel sliding 

guard monitoring with 

short circuit and earth 

fault monitoring. 
(category 4, up to PL e) 

Emergency Stop 

Circuit 

Fig. 6: 

Monitored manual start

It is monitored that the start 

button was opened before the 

emergency stop button closes. 

(Prerequisite: operating voltage 

must not be interrupted) 

Fig. 7: 

Automatic start (e.g. for application with 

a safety door). 
Max perm. delay during closing of the 

safety switches on S12 and S13: 
S12 before S13: 300ms;  
S13 before S12: any  

Warning: 
Safety contacts switch 

when the power supply is 

connected. 

Fig. 8: 

Feedback loop for monitored manual 

start: 
The feedback loop monitors contactors 

or the expansion modules . 

Starting Behavior 

Feedback Loop 

Note:  The items listed under “Electrical connection” must be observed during commissioning. 

Commissioning 

Procedure 

1. Wiring emergency stop circuit: 
Wire  the  emergency  stop  circuit  according  to  the  required 

Performance Level determined (see Fig. 1 to Fig 5). 
2. Wiring start circuit: 
Wire the start circuit according to Fig. 6 or Fig. 7 to set the 

starting behavior. 
Warning: 
If “Automatic start” is set, bear in mind that the safety con-

tacts  will  switch  immediately  after  the  power  supply  is 

connected.  If  “Monitored  manual  start”  is  set,  the  start 

button must be opened after wiring.  
3. Wiring feedback loop: 
If  your  application  provides  for  external  contactors  or  ex-

pansion modules, connect them to the device according to 

Fig. 8 or Fig. 9. 
4. Wiring power supply: 
Connect the power supply to terminals A1 and A2 (Fig. 10). 
Warning:  Wiring only in de-energized state. 
5. Set time delay:  
Set the desired time delay on the rotary knob  

Warning:  
Scale  divisions  should  be  regarding  only  as  a  setting  aid. 

Always make shure to measure the delay time. 
6. Starting the device: 
Switch on the operating voltage. 
Warning: 
If  the  “Automatic  start”  starting  behavior  is  set,  the  safety 

contacts will close immediately. 
If the “Monitored manual start” starting behavior is set, close 

the start button to close the safety contacts. 
LEDs K1, K2, K3 and K4 are lit. 
7. Triggering safety function: 
Open  the  emergency  stop  circuit by  actuating  the  connec-

ted safety switch. The safety contacts open immediately. 
Warning:  Messen Sie die Verzögerungszeit. 
8. Reactivation: 
Close  the  emergency  stop  circuit.  If  “Automatic  start”  is 

selected, the safety contacts will close immediately. 
If the “Monitored manual start” starting behavior is set, close 

the start button to close the safety contacts. 

Warning:  
In  order  to  activate  earth  fault  monitoring,  the  PE  must  be 

connected only to the power supply unit in accordance with 

EN60204-1.

 

Fig. 5: 

Two-channel emergency stop 

with pnp-outputs/OSSD-outputs 
with  short circuit monitoring. 
(category 4,  up to PL e) 

Fig. 9: 

Feedback loop for automatic start: 
The feedback loop monitors contac-

tors or the expansion modules . 

Power supply  
and  
Safety contacts 

Fig. 10: 

Power supply A1 and A2. 
 
(Power supply according to techn. 

Data ) 

Fig. 11: 

Connecting load to safety contacts. 
 
(Figure shows example.  
Voltage „+V“ according to techn. 

Data) 

SR107AD, SR108AD, SR109AD 

User Information for SR107AD, SR108AD, SR109AD 

Summary of Contents for SR107AD

Page 1: ... device is incorporated must be validated by the user Failure to observe the safety regulations can result in death serious injury and serious damage Installation As per DIN EN 60204 1 the device is intended for installa tion in control cabinets with a minimum degree of protection of IP54 It is mounted on a 35 mm DIN rail according to DIN EN 60715 TH35 Safety Precautions Installation and commissio...

Page 2: ...acts will switch immediately after the power supply is connected If Monitored manual start is set the start button must be opened after wiring 3 Wiring feedback loop If your application provides for external contactors or ex pansion modules connect them to the device according to Fig 8 or Fig 9 4 Wiring power supply Connect the power supply to terminals A1 and A2 Fig 10 Warning Wiring only in de e...

Page 3: ...1 C A r o f A 3 V 0 5 2 d a o l c i m o r o f A 8 V 0 5 C D 3 1 C D r o f A 3 V 4 2 Max cumulative current on the safety contacts 15A e l b a t s u j d a y l s u o u n i t n o c s 0 3 1 y a l e d e m i T A m 0 2 V 4 2 d a o l t c a t n o c m u m i n i M G g A 0 1 A 8 F A 6 T s e s u f t c a t n o c n i M m m 5 2 4 1 0 n o i t c e s s s o r c e n i l x a M 2 m m 5 7 0 t a m 0 0 0 1 e n i l l o r t ...

Page 4: ...w and that the related standards have been applied OMRON Scientific Technologies Inc 6550 Dumbarton Circle Fremont CA 94555 U S A Directives applied EMC directive 2004 108 EC Machinery directive 2006 42 EC Fremont April 2017 The signed EC Declaration of Conformity is included with the product RoHS directive 2002 95 EC Vanessa Chen Quality Manager Authorized Signer of Declarations of Conformity OMR...

Reviews: