background image

S8VK-WA

5

Inrush Current, Startup Time, and Output Hold Time

Note:

Twice the normal inrush current will flow during parallel 
operation or for backup operation. Therefore, check the fusing 
characteristics of fuses and operating characteristics of 
breakers making sure that the external fuses will not burn out 
and the circuit breakers will not be activated by the inrush 
current.

Overload Protection

The product is automatically protected from short-circuit current and 
overcurrent damages when the load current is in the range of 151 to 
175% of the rated current.
When the output current falls within the rated range, the overload 
protection function is automatically cleared.

Note: 1.

Internal parts may occasionally deteriorate or be damaged 
if a short-circuited or overcurrent state continues during 
operation. Be sure to check that the Iout > 100% indicator is 
not lit or the Iout > 100% signal output is turned OFF before 
using.

2.

Internal parts may possibly deteriorate or be damaged if the 
Power Supply is used for applications with inrush current or 
overloading at the load end. Do not use the Power Supply 
for such applications.

Overvoltage Protection

Overvoltage will be detected to prevent the load from being subjected 
to excessive voltage when the feedback circuit in the Power Supply 
fails, etc.
When an excessive voltage that is approximately 130% of the rated 
output voltage or more is output, the output voltage is cut OFF, 
preventing damage to the load due to overvoltage.
Reset the input power by turning it OFF for at least three minutes and 
then turning it back ON again.

Note:

Do not turn ON the power again until the cause of the 
overvoltage has been removed.

INPUT OK Indicator

The INPUT OK indicator will light when the input voltage exceeds the 
lower limit value of the permissible range.

Note:

The voltage may be applied even if the indicator does not light. 
Be sure to check the input voltage when performing wiring.

DC OK Indicator/Signal Output 

The DC OK indicator will light when the output voltage is more than 
90% of the rated output voltage, and the internal MOS FET relay is 
conducted (turned ON).

Note: 1.

The output voltage may be generated even if the indicator 
does not light. Be sure to check the output voltage when 
connecting to the load.

2.

This function monitors the voltage at the power output 
terminals.
To check the voltage accurately, measure the voltage at the 
load end.

3.

If the output voltage is set to less than 90% of the rated 
output voltage, the indicator may go off and the signal 
output may be turned OFF.

Iout > 100% Indicator/Signal Output

The Iout > 100% indicator lights up when the output current exceeds 
the rated output current, and the internal MOS FET relay is conducted 
(turned ON).

Note: 1.

The Iout > 100% Indicator may light up, and the Iout > 100% 
Signal Output may turn ON during peak current operation, 
however, the Power Supply can be used as long as the 
operating conditions specified in 

Peak current

 (P.14) are 

satisfied.

2.

Even when the operating conditions for parallel operation 
are satisfied, the Iout>100% Indicator / Signal Output may 
operate, so do not use the Iout>100% Indicator / Signal 
Output.

3.

During a short-circuit, the indicator will operate intermittently 
due to the overload protection function. When this happens, 
the indicator will blink in accordance with the intermittent 
operation, and the Iout > 100% signal output will repeated 
turn ON and OFF.
The shortest ON time of the Iout > 100% signal output 
during intermittent operation is 5 ms.

Specifications of the Signal Output Terminals 
(between DC OK Signal Output Terminal and 
COM Terminal, and between Iout > 100% Signal 
Output Terminal and COM Terminal)

Since the Signal Output is composed of the MOS FET relay, it does 
not have any polarity.
30 VDC max., 50 mA max.
Residual voltage when the function is ON: 2 V max. 
Leakage current when the function is OFF: 0.1 mA max.

Note: 1.

Internal current control circuits are not provided internally 
for output signals. Do not allow the output current to exceed 
50 mA.

2.

After completing wiring, confirm that the circuits operate 
correctly.

Hold time

O

u

tp

u

v

oltage

Inr

u

sh c

u

rrent on inp

u

t application

90

%

96.5

%

Inp

u

t O

N

AC inp

u

v

oltage

AC inp

u

c

u

rrent

Inp

u

t OFF

Start

u

p time

O

u

tp

u

t c

u

rrent (

%

)

Intermittent operation

0

100

O

u

tp

u

v

oltage (

V

)

Summary of Contents for S8VK-WA Series

Page 1: ...put UL 121201 acquired Certification for 3 000 m altitude UL EN IEC 62368 1 EN 50178 EN 62477 1 1 Conforms to EN IEC 61558 2 16 Coated PCBs for Better Resistance to Environment Warranty Five years 3 1...

Page 2: ...Maximum boost current Model 240 W Three phase single phase 200 to 240 VAC Allowable range Three phase single phase 170 to 264 VAC 240 to 350 VDC 24 V 10 A 15 A S8VK WA24024 480 W 24 V 20 A 30 A S8VK W...

Page 3: ...fer to Overload Protection on page 5 Overvoltage protection Yes 130 or higher of rated output voltage power shut off shut off the input voltage and turn on the input again Refer to Overvoltage Protect...

Page 4: ...details Standard Compliance To comply with PELV output requirements for EN IEC 60204 1 ground the negative side of the output V to a protective earth PE EN IEC 61558 2 16 The S8VK WA was designed bas...

Page 5: ...90 of the rated output voltage and the internal MOS FET relay is conducted turned ON Note 1 The output voltage may be generated even if the indicator does not light Be sure to check the output voltag...

Page 6: ...th less load or larger output capacity The product may have failed or the overvoltage protection may have been activated for the product To check for overvoltage protection turn the input power OFF an...

Page 7: ...oothing circuit Harmonic current suppression circuit DC OK COM DC OUTPUT L1 1 INPUT L1 2 L2 1 L2 2 L3 2 L3 1 out I 100 S8VK WA48024 480 W Overcurrent detection circuit Current detection circuit Smooth...

Page 8: ...V2 10 V1 11 V2 12 V3 13 INPUT OK Indicator INPUT OK Green Lights up when the input voltage exceeds the lower limit value of the permissible range 14 Iout 100 Indicator Iout 100 Yellow The Iout 100 In...

Page 9: ...s applied C Front side by side mounting This Power Supply can be used at an altitude of up to 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve 240 W 480 W Ho...

Page 10: ...W20F Front mounting bracket For 480 W models S82Y VKW40F 1 1 5 2 8 0 max when sliding 5 17 3 117 111 4 5 4 15 8 54 4 53 8 5 4 6 5 0 55 19 8 1 2 0 6 121 4 1 55 1 0 6 124 1 10 S8VK WA24024 5 2 8 0 max w...

Page 11: ...cted to sliding to either side attach an End Plate PFP M on each side of the Unit Mounting Rail Material Aluminum PFP 100N PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 ind...

Page 12: ...dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when mounting Do not use in locations where the ambient temperature...

Page 13: ...move the sheet covering the S8M for machining before power ON so that it does not interfere with heat dissipation If there is a possibility of vibration or shock please use wires and stranded wires wi...

Page 14: ...t flow Duty 30 Do not allow the peak current to continue for more than 10 seconds Do not allow the duty to exceed 30 The Power Supply may be damaged Ensure that the average current of one cycle of the...

Page 15: ...ge of 25 V max Adjust the output voltage difference of each Power Supply to 50 mV or less using the output voltage adjuster V ADJ There is no current balancing function for S8VK X A high output voltag...

Page 16: ...e screwdriver and pull out the Block Connecting Wires to the Push In Plus Terminal Block Part Names of the Terminal Block Connecting Wires with Ferrules and Solid Wires Insert the solid wire or ferrul...

Page 17: ...nals COM Terminals Note 1 Make sure that the outer diameter of the wire is smaller than the inner diameter of the insulating sleeve of the recommended ferrule 2 Make sure that the ferrule processing d...

Page 18: ...he overload protection or overvoltage protection has operated The internal protection may operate if a large amount of surge voltage such as a lightning inrush is applied to the input In case there is...

Page 19: ...eration of these components to achieve the original Power Supply functions and performance However the influence of the ambient temperature on aluminum electrolytic capacitors is large and the service...

Page 20: ...MEMO 20...

Page 21: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 22: ...U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto...