Recommended circuit breakers and fuses

• Product failure may result in fire or electric shocks. Therefore, 

always use the recommended circuit breaker or fuse.

• To ensure conformance to safety standards, and secure safety of 

the Unit, connect an input to the Unit via the recommended circuit 
breakers or fuses indicated in the table below.

• If multiple Units are used through crossover wiring, select the 

circuit breaker or fuse in view of the input current and inrush 
current.

Wiring method

• Connect the input as shown in the figure below.
• In the case of a three-phase four-wire system, do not connect the 

ground and neutral wire, but connect the other three wires to “L1/
+, L2, L3/-”.

Wiring

• This is the protective earth terminal specified in the safety 

standards. Connect the ground completely. Electric shock or 
malfunction may occur if the ground is not connected completely.

• Minor fire may possibly occur. Ensure that DC input and output 

terminals are wired correctly.

• When you insert wires or insert a screwdriver into a release hole, 

do not press down on the terminal block with a force of 40 N or 
greater.

• Do not wire anything to the release holes.
• Do not tilt or twist a flat-blade screwdriver while it is inserted into a 

release hole on the terminal block. The terminal block may be 
damaged.

• Insert a flat-blade screwdriver into the release holes at an angle. 

The terminal block may be damaged if you insert the screwdriver 
straight in.

• Do not allow the flat-blade screwdriver to fall out while it is inserted 

into a release hole.

• Do not bend a wire past its natural bending radius or pull on it with 

excessive force. This may cause a wire to be broken.

• Do not insert more than one wire into each terminal insertion hole.
• Do not pre-solder the ends of the wires. Doing so will inhibit proper 

connection.

• Be sure to remove the sheet covering the S8M for machining 

before power-ON so that it does not interfere with heat dissipation.

• If there is a possibility of vibration or shock, please use wires and 

stranded wires with ferrules.

• Minor fire may occasionally occur.

Always check the voltage of the equipment when replacing the 
Unit, and be sure to use a conforming product.

• Use the following material for the wires after confirming the rating 

of the wires in order to prevent smoking or ignition.

Recommended Wire Type

• Input crossover wiring can be used for the input side of this Power 

Supply.

• Do not use crossover wiring for more than five Power Supplies, 

and do not allow the steady-state current to the input terminals to 
exceed 10 A. The above table gives the recommended wires for 
one Power Supply.

• If you use crossover wiring for N number of Power Supplies, a 

current that is N times the current for a standalone Power Supply 
may flow to the input terminals. Take this into consideration when 
you select wiring materials.

Model

Input

Recommended product

(per single Unit)

S8VK-WA24024

Three-phase

Circuit breaker:

240 VAC min., 4 to 20 A, Type B, 

C, or D characteristics

Single-phase

Circuit breaker:

240 VAC min., 4 to 20 A, Type B, 

C, or D characteristics

DC

Fuse: 

Fast-acting type, 350 VDC min., 6 A

S8VK-WA48024

Three-phase

Circuit breaker:

240 VAC min., 4 to 20 A, Type B, 

C, or D characteristics

Single-phase

Circuit breaker:

240 VAC min., 7 to 20 A, Type B, 

C, or D characteristics

DC

Fuse: 

Fast-acting type, 350 VDC min., 8 A

L1
L2
L3
N
PE

TN-S

TN-C

PEN

L3

L2

L1

Single-phase

PE

N

L

Input wiring (TN-S, TN-C, single-phase)

Circuit 
breaker

Circuit 
breaker

Circuit 
breaker

Input wiring (TT, IT, DC)

L1
L2
L3
N

TT

DC

PE

-

+

IT

L3

L2

L1

Circuit 
breaker

Circuit 
breaker

Fuse

Terminal

Model

Recommended wire 

gauge

(mm

2

)

(AWG)

Input

S8VK-WA24024

0.34 to 2.5

22 to 14

S8VK-WA48024

0.5 to 2.5

20 to 14

DC Output

S8VK-WA24024

2 to 2.5

14

S8VK-WA48024

3.5 to 6

12 to 10

Signal Output/COM

S8VK-WA

@@@

24

0.25 to 2.5

24 to 14

PE (protective 

earth) terminal

S8VK-WA

@@@

24

2 to 2.5

14

Summary of Contents for S8VK-WA Series

Page 1: ...put UL 121201 acquired Certification for 3 000 m altitude UL EN IEC 62368 1 EN 50178 EN 62477 1 1 Conforms to EN IEC 61558 2 16 Coated PCBs for Better Resistance to Environment Warranty Five years 3 1...

Page 2: ...Maximum boost current Model 240 W Three phase single phase 200 to 240 VAC Allowable range Three phase single phase 170 to 264 VAC 240 to 350 VDC 24 V 10 A 15 A S8VK WA24024 480 W 24 V 20 A 30 A S8VK W...

Page 3: ...fer to Overload Protection on page 5 Overvoltage protection Yes 130 or higher of rated output voltage power shut off shut off the input voltage and turn on the input again Refer to Overvoltage Protect...

Page 4: ...details Standard Compliance To comply with PELV output requirements for EN IEC 60204 1 ground the negative side of the output V to a protective earth PE EN IEC 61558 2 16 The S8VK WA was designed bas...

Page 5: ...90 of the rated output voltage and the internal MOS FET relay is conducted turned ON Note 1 The output voltage may be generated even if the indicator does not light Be sure to check the output voltag...

Page 6: ...th less load or larger output capacity The product may have failed or the overvoltage protection may have been activated for the product To check for overvoltage protection turn the input power OFF an...

Page 7: ...oothing circuit Harmonic current suppression circuit DC OK COM DC OUTPUT L1 1 INPUT L1 2 L2 1 L2 2 L3 2 L3 1 out I 100 S8VK WA48024 480 W Overcurrent detection circuit Current detection circuit Smooth...

Page 8: ...V2 10 V1 11 V2 12 V3 13 INPUT OK Indicator INPUT OK Green Lights up when the input voltage exceeds the lower limit value of the permissible range 14 Iout 100 Indicator Iout 100 Yellow The Iout 100 In...

Page 9: ...s applied C Front side by side mounting This Power Supply can be used at an altitude of up to 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve 240 W 480 W Ho...

Page 10: ...W20F Front mounting bracket For 480 W models S82Y VKW40F 1 1 5 2 8 0 max when sliding 5 17 3 117 111 4 5 4 15 8 54 4 53 8 5 4 6 5 0 55 19 8 1 2 0 6 121 4 1 55 1 0 6 124 1 10 S8VK WA24024 5 2 8 0 max w...

Page 11: ...cted to sliding to either side attach an End Plate PFP M on each side of the Unit Mounting Rail Material Aluminum PFP 100N PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 ind...

Page 12: ...dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when mounting Do not use in locations where the ambient temperature...

Page 13: ...move the sheet covering the S8M for machining before power ON so that it does not interfere with heat dissipation If there is a possibility of vibration or shock please use wires and stranded wires wi...

Page 14: ...t flow Duty 30 Do not allow the peak current to continue for more than 10 seconds Do not allow the duty to exceed 30 The Power Supply may be damaged Ensure that the average current of one cycle of the...

Page 15: ...ge of 25 V max Adjust the output voltage difference of each Power Supply to 50 mV or less using the output voltage adjuster V ADJ There is no current balancing function for S8VK X A high output voltag...

Page 16: ...e screwdriver and pull out the Block Connecting Wires to the Push In Plus Terminal Block Part Names of the Terminal Block Connecting Wires with Ferrules and Solid Wires Insert the solid wire or ferrul...

Page 17: ...nals COM Terminals Note 1 Make sure that the outer diameter of the wire is smaller than the inner diameter of the insulating sleeve of the recommended ferrule 2 Make sure that the ferrule processing d...

Page 18: ...he overload protection or overvoltage protection has operated The internal protection may operate if a large amount of surge voltage such as a lightning inrush is applied to the input In case there is...

Page 19: ...eration of these components to achieve the original Power Supply functions and performance However the influence of the ambient temperature on aluminum electrolytic capacitors is large and the service...

Page 20: ...MEMO 20...

Page 21: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 22: ...U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto...

Reviews: