background image

S8VK-WA

3

Ratings, Characteristics, and Functions

Note:

For 

*

1 to 

*

12, refer to page 4.

Power rating

240 W

480 W

Item

Output voltage

24 V

24 V

Efficiency 

*

1

Three-phase 200 VAC input 

93% typ.

94% typ.

Single-phase 200 VAC input

92% typ.

93% typ.

Three-phase 230 VAC input 

93% typ.

94% typ.

Single-phase 230 VAC input

93% typ.

94% typ.

Input con-
ditions

Input voltage range 

*

2

Three-phase/single-phase 170 to 264 VAC, 265 to 300 VAC (1 second) 
240 to 350 VDC

Frequency 

*

2

50/60 Hz (47 to 63 Hz)

Input current 

*

1

Three-phase 200 VAC input 

0.80 A typ. 

1.6 A typ. 

Single-phase 200 VAC input

1.4 A typ. 

2.6 A typ. 

Three-phase 230 VAC input 

0.70 A typ. 

1.4 A typ. 

Single-phase 230 VAC input

1.2 A typ. 

2.3 A typ. 

Power factor

0.9 min.

Leakage current 

*

3

Three-phase 200 VAC input

1 mA max.

Three-phase 230 VAC input 

1 mA max.

Inrush current 

*

4

(for a cold start at 25°C)

Three-phase 200 VAC input

13 A typ. 

13 A typ. 

Three-phase 230 VAC input 

15 A typ. 

15 A typ. 

Output 
character-
istics

Rated output current

10 A

20 A

Power Boost Function

15 A

30 A

Voltage adjustment range 

*

5

24 to 29.5 V (with V.ADJ)

Ripple noise voltage 

*

6 Three-phase 

200 to 240 VAC input

50 mVp-p max.
at 20 MHz of bandwidth

120 mVp-p max.
at 20 MHz of bandwidth

Input variation influence 

*

7

0.5% max.

Load variation influence 

*

8

1.5% max.

Temperature variation 
influence

200 to 240 VAC input

0.05%/°C max.

Startup time 

*

9

Three-phase 200 VAC input 

1,000 ms max.

Three-phase 230 VAC input 

1,000 ms max.

Output hold time 

*

9

Three-phase 200 VAC input 

35 ms typ. 

30 ms typ. 

Three-phase 230 VAC input 

35 ms typ. 

30 ms typ. 

Additional 
functions

Overload protection 

Yes, automatic reset, intermittent operation type
Refer to 

Overload Protection

 on page 5.

Overvoltage protection

Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and 
turn on the input again),
Refer to 

Overvoltage Protection

 on page 5.

Series operation

Yes (For up to two Power Supplies; external diodes required.)

Parallel operation

Yes (For up to two Power Supplies), Refer to 

Parallel Operation

 on page 15.

INPUT OK Indicator

Yes (LED: Green)

DC OK Indicator

Yes (LED: Green)

Iout > 100% Indicator

Yes (LED: Yellow)

DC OK Signal Output

Yes (MOS FET relay output 30 VDC max., 50 mA max.)

Iout > 100% signal output

Yes (MOS FET relay output 30 VDC max., 50 mA max.)

Insulation

Withstand voltage

3.0 kVAC for 1 min. (between all input terminals and all output terminals), cutoff current 20 mA

2.0 kVAC for 1 min. (between all input terminals and PE terminals), cutoff current 20 mA

1.0 kVAC for 1 min. (between all output terminals, signal output terminals and PE terminals), 
cutoff current 25 mA

0.5 kVAC for 1 min. (between all output terminals and all signal output terminals), cutoff 
current 10 mA

Insulation resistance

100 M

Ω

 min. (between all output terminals, signal output terminals and all input terminals / 

PE terminals) at 500 VDC

Environ-
ment

Ambient operating temperature *10

-40 to 70

°

C (Derating is required according to the temperature. Refer to 

Engineering Data

 

on page 9.) (with no condensation or icing)

Storage temperature

-40 to 85°C (with no condensation or icing)

Ambient operating humidity

95% max. (Storage humidity: 95% max.)

Vibration resistance

10 to 55 Hz, maximum 5 G, 0.42 mm single amplitude for 2 h each in X, Y, and Z directions

Shock resistance

294 m/s

2

, 3 times each in ±X, ±Y, ±Z directions

Reliability

MTBF 

*

11

290,000 hrs typ.

230,000 hrs typ.

Expected life 

*

12

10 years min.

Construc-
tion

Weight

800 g max.

1050 g max.

Cooling fan

No

Degree of protection

IP20 by EN/IEC 60529

Summary of Contents for S8VK-WA Series

Page 1: ...put UL 121201 acquired Certification for 3 000 m altitude UL EN IEC 62368 1 EN 50178 EN 62477 1 1 Conforms to EN IEC 61558 2 16 Coated PCBs for Better Resistance to Environment Warranty Five years 3 1...

Page 2: ...Maximum boost current Model 240 W Three phase single phase 200 to 240 VAC Allowable range Three phase single phase 170 to 264 VAC 240 to 350 VDC 24 V 10 A 15 A S8VK WA24024 480 W 24 V 20 A 30 A S8VK W...

Page 3: ...fer to Overload Protection on page 5 Overvoltage protection Yes 130 or higher of rated output voltage power shut off shut off the input voltage and turn on the input again Refer to Overvoltage Protect...

Page 4: ...details Standard Compliance To comply with PELV output requirements for EN IEC 60204 1 ground the negative side of the output V to a protective earth PE EN IEC 61558 2 16 The S8VK WA was designed bas...

Page 5: ...90 of the rated output voltage and the internal MOS FET relay is conducted turned ON Note 1 The output voltage may be generated even if the indicator does not light Be sure to check the output voltag...

Page 6: ...th less load or larger output capacity The product may have failed or the overvoltage protection may have been activated for the product To check for overvoltage protection turn the input power OFF an...

Page 7: ...oothing circuit Harmonic current suppression circuit DC OK COM DC OUTPUT L1 1 INPUT L1 2 L2 1 L2 2 L3 2 L3 1 out I 100 S8VK WA48024 480 W Overcurrent detection circuit Current detection circuit Smooth...

Page 8: ...V2 10 V1 11 V2 12 V3 13 INPUT OK Indicator INPUT OK Green Lights up when the input voltage exceeds the lower limit value of the permissible range 14 Iout 100 Indicator Iout 100 Yellow The Iout 100 In...

Page 9: ...s applied C Front side by side mounting This Power Supply can be used at an altitude of up to 3 000 m Between 2 000 and 3 000 m derate the load according to the following derating curve 240 W 480 W Ho...

Page 10: ...W20F Front mounting bracket For 480 W models S82Y VKW40F 1 1 5 2 8 0 max when sliding 5 17 3 117 111 4 5 4 15 8 54 4 53 8 5 4 6 5 0 55 19 8 1 2 0 6 121 4 1 55 1 0 6 124 1 10 S8VK WA24024 5 2 8 0 max w...

Page 11: ...cted to sliding to either side attach an End Plate PFP M on each side of the Unit Mounting Rail Material Aluminum PFP 100N PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 ind...

Page 12: ...dissipation to increase the long term reliability of the Power Supply Be sure to allow convection in the atmosphere around devices when mounting Do not use in locations where the ambient temperature...

Page 13: ...move the sheet covering the S8M for machining before power ON so that it does not interfere with heat dissipation If there is a possibility of vibration or shock please use wires and stranded wires wi...

Page 14: ...t flow Duty 30 Do not allow the peak current to continue for more than 10 seconds Do not allow the duty to exceed 30 The Power Supply may be damaged Ensure that the average current of one cycle of the...

Page 15: ...ge of 25 V max Adjust the output voltage difference of each Power Supply to 50 mV or less using the output voltage adjuster V ADJ There is no current balancing function for S8VK X A high output voltag...

Page 16: ...e screwdriver and pull out the Block Connecting Wires to the Push In Plus Terminal Block Part Names of the Terminal Block Connecting Wires with Ferrules and Solid Wires Insert the solid wire or ferrul...

Page 17: ...nals COM Terminals Note 1 Make sure that the outer diameter of the wire is smaller than the inner diameter of the insulating sleeve of the recommended ferrule 2 Make sure that the ferrule processing d...

Page 18: ...he overload protection or overvoltage protection has operated The internal protection may operate if a large amount of surge voltage such as a lightning inrush is applied to the input In case there is...

Page 19: ...eration of these components to achieve the original Power Supply functions and performance However the influence of the ambient temperature on aluminum electrolytic capacitors is large and the service...

Page 20: ...MEMO 20...

Page 21: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 22: ...U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto...