background image

S8PS

S8PS

2

Specifications

 Ratings/Characteristics

Item

50 W

100 W

150 W

300 W

600 W

Efficiency (typical)

75 to 87% (depends on the model)

Input

Voltage

100 to 240 VAC (85 to 264 VAC)

Input

Frequency

47 to 450 Hz

Current (see note 1)

0.9 or 0.45 A
max.

1.8 or 0.9 A
max.

2.7 or 1.4 A
max.

5.4 or 2.7 A
max.

10 or 5 A max.

Power factor (see note 1)

0.95 TYP.

Leakage current (see note 1)

0.5 or 1.0 mA max.

Inrush current (25

°

C, cold start) (see note 1)

25 or 50 A max.

Output

Voltage adjustment range

–5% to 10%

Output

Ripple (see note 1)

2% (p–p) max.

Input variation influence

0.4% max. (at 85 to 132 VAC input/at 170 to 264 VAC input, 100% load)

Load variation influence

0.8% max. (with rated input, 0 to 100% load)

Temperature variation influence (see note 1)

0.05%/

°

C max.

Rise time

1,000 ms max. (up to 90% of output voltage at rated output voltage/current)

Hold time (see note 1)

20 ms min.

Additional
function

Overload protection

105% min., voltage trailing intermittent operation 
(With the 600-W model, output is turned OFF at 5 s min.)

function

Overvoltage protection

Yes

Overheat protection

No

Yes

Protection-ON alarm indicator

No

Yes (Red)

Parallel operation

No

Yes, 2 units max.

Other

Heat radiation

Natural air-cooling

Fan

Other

Ambient temperature

Operating: See the derating curve in the 

Engineering Data

 section. (with no condensation

nor icing)

nor icing)
Storage: –25

°

C to 65

°

C (with no condensation nor icing)

Ambient humidity

25% to 85%

Dielectric strength

3.0 kVAC, 50/60 Hz for 1 min (between all inputs and outputs)
2.2 kVAC, 50/60 Hz for 1 min (between all inputs and GR terminals)
1 kVAC, 50/60 Hz for 1 min (between all outputs and GR terminals)

Insulation resistance

100 M

 min. (between all output and input/GR terminals at 500 VDC)

Vibration resistance

10 to 55 Hz, 0.75-mm amplitude for 2 h each in X, Y, and Z directions

Shock resistance

300 m/s

2

 (approx. 30G), 3 times each in 

±

X, 

±

Y, and 

±

Z directions

Output indicator

Yes (green)

Terminal screw tightening torque

1.08 N 

S

 m {11 kgf 

S

 cm} (see note 2)

Electromagnetic interference

Conforms to FCC Class B, EN50081-1

EMC

(EMI):

EN50081-1

Emission Enclosure:

EN55022 class B

Emission AC Mains:

EN55022 class B

Harmonic Current:

EN61000-3-2

(EMS):

EN50082-2

Immunity ESD:

EN61000-4-2:

4-kV contact discharge (level 2)
8-kV air discharge (level 3)

Immunity RF-interference:

ENV50140:

10 V/m (80 MHz to 1 GHz) (level 3)

Immunity Conducted Disturbance: ENV50141:

10 V (0.15 to 80 MHz) (level 3)

Immunity Burst:

EN61000-4-4:

2-kV power-line (level 3)
2-kV output line (level 4)

Immunity Surge:

EN61000-4-5:

between 3-kV lines
between 4.5-kV line and FG

Approved standards

UL508, UL1012, CSA C22.2 No. 950, CSA C22.2 No. 14, EN60950, VDE0160.
Conforms to UL1950 and CSA E.B. 1402C

Reliability (MTBF) (see note 3)

135,000 hrs min.

60,000 hrs min.

Life expectancy (see note 4)

10 yrs. min. (Used at 40

°

C at the rated input with a 50% load, standard installation)

Weight (see note 5)

420 g max.

600 g max.

900 g max.

2,200 g max.

3,500 g max.

Mounting method

Front-mounting Bracket or DIN Track Mounting Bracket

Front-mounting Bracket

Note:

1. 100% load for rated input voltage (100 VAC or 200 VAC)
2. Do not press down on the terminal block with a force exceeding 75 N {7.6 kgf} while tightening the terminals.
3. MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and

indicates reliability of devices. Therefore, it does not necessarily represent a life of the product.

4. The life expectancy shown in the above table indicates average operating hours under the ambient temperature of 40

°

C and a load

rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. It must be noted that
the life expectancy of the fan built into the 600-W model is not included.

5. The weight indicated is for the open-frame type. (Includes the cover for 300-W and 600-W models.)

Summary of Contents for S8PS Series

Page 1: ...Power ratings Output voltage Output current Front mounting Bracket DIN Track Mounting Bracket Covered type 100 to 240 VAC 50 W 5 V 10 A S8PS 05005C S8PS 05005CD Co e ed y e 00 o 0 C 50 12 V 4 2 A S8PS...

Page 2: ...s2 approx 30G 3 times each in X Y and Z directions Output indicator Yes green Terminal screw tightening torque 1 08 N S m 11 kgf S cm see note 2 Electromagnetic interference Conforms to FCC Class B E...

Page 3: ...on 600 W Model 20 mm min 20 mm min 20 mm min 20 mm min 30 mm min 30 mm min 20 mm min 20 mm min 30 mm min 30 mm min 20 mm min 20 mm min 20 mm min 20 mm min 20 mm min 20 mm min 50 to 150 W Model Natural...

Page 4: ...ercurrent condition continued otherwise the internal elements of the S8PS may be dam aged or broken Overvoltage Protection The Power Supply is provided with an overvoltage protection func tion that pr...

Page 5: ...hing circuit Detector Control circuit Overload detection circuit Overload detection circuit Harmonic current control Smooth ing Overload detection circuit Overload detection circuit Rectifier smoothin...

Page 6: ...h 6 max Front mounting Bracket for 50 W Models Mounting Holes Using the Mounting Bracket Attach the Mounting Bracket to the panel and loosely tighten the two screws Insert the projected parts of the B...

Page 7: ...ounting Bracket for 100 150 W Models Dimensions with Mounting Bracket Using the Mounting Bracket S8PS 30024C 300 W Eight M4 depth 8 max also for the opposite side Mounting holes also on opposite side...

Page 8: ...our M4 depth 8 max 300 W models 600 W models Four M4 Four M4 10 dia Two 5 dia 600 W models Note Mount the Unit 21 6 mm away from the mounting surface in order to provide air ventilation on the rear si...

Page 9: ...y Unit when the Unit is shipped S8PS 10024D 100 W S8PS 10024CD 100 W S8PS 15024D 150 W S8PS 15024CD 150 W Five M4 terminal screws 3 5 dia 11 5 max 5 6 With slide 9 max Five M4 terminal screws 4 5 dia...

Page 10: ...Order Separately PFP 100N PFP 50N 4 5 15 25 25 25 25 10 10 1 000 500 see note 7 3 0 15 35 0 3 27 0 15 1 4 5 15 25 25 25 25 15 10 10 1 000 35 0 3 27 24 16 29 2 1 1 5 PFP 100N2 15 5 see note Note The va...

Page 11: ...been turned OFF Doing so may result in electric shock due to a residual voltage Do not touch the S8PS or heat radiation fin while the power is being supplied or immediately after the power is turned...

Page 12: ...dust As a preventive maintenance measure replace the fan within two years if it is used at an ambient temperature of 40 C Fans are available as replacements Model S82Y JFAN Fan Set Fan above four M4 x...

Reviews: