S8PS

S8PS

4

 Overload Protection

50- to 300-W Models

The Power Supply is provided with an overload protection function
that protects the load and the power supply from possible damage
by overcurrent. The protection function operates when the load cur-
rent rises above an overcurrent set value (105% of the rated load
current). For a short-circuit or overcurrent lasting less than 20 se-
conds, output voltage is decreased to protect equipment. When the
output current falls within the rated range, the overload protection
function is automatically cleared.

Output voltage  (V)

Output current (%)

Rating

Intermittent
operation

Note:

Do not continue using the S8PS under short-circuited or
overcurrent conditions for longer than 20 seconds, other-
wise the internal elements of the S8PS may be damaged or
broken.

600-W Models

If an excessive current flows for 5 s or more, the output will be turned
OFF and simultaneously protection-ON alarm indicator will be lit. To
reset the S8PS, turn OFF the input voltage, leave the S8PS for at
least three minutes, and then apply the input voltage again.

Note:

Do not continue using the S8PS with the output terminals
short-circuited or the overcurrent condition continued,
otherwise the internal elements of the S8PS may be dam-
aged or broken.

 Overvoltage Protection

The Power Supply is provided with an overvoltage protection func-
tion that protects the load and the Power Supply from possible dam-
age by overvoltage. When the output voltage rises above a set val-
ue (115% of the rated output voltage), the protection function is trig-
gered, shutting OFF the output voltage. If this occurs, reset the Pow-
er Supply by turning it OFF for 1 minute min. and then turning it ON
again.

Rated output
voltage

Output voltage (V)

Overvoltage
protection
operating

Variable range

0 V

300- and 600-W Models Only

The overvoltage protection-ON alarm indicator lights when the
function is operating.

 Overheat Protection Function

600-W Model Only

If the internal temperature of the S8PS rises excessively as a result
of fan failure or any other reason, the overheat protection circuit will
be triggered to protect the internal elements of the S8PS and simul-
taneously a protection-ON alarm indicator will be lit. To reset the
S8PS turn OFF the input voltage, leave the S8PS for at least one
minute and then apply the input voltage again.

 Inrush Current, Rise Time, Hold Time

Input ON

Input OFF

AC input
voltage

AC input
current

Output
voltage

Rise time
(1,000 ms max.)

Hold time
(20 ms min.)

Inrush current on input application

90%

96.5%

Summary of Contents for S8PS Series

Page 1: ...Power ratings Output voltage Output current Front mounting Bracket DIN Track Mounting Bracket Covered type 100 to 240 VAC 50 W 5 V 10 A S8PS 05005C S8PS 05005CD Co e ed y e 00 o 0 C 50 12 V 4 2 A S8PS...

Page 2: ...s2 approx 30G 3 times each in X Y and Z directions Output indicator Yes green Terminal screw tightening torque 1 08 N S m 11 kgf S cm see note 2 Electromagnetic interference Conforms to FCC Class B E...

Page 3: ...on 600 W Model 20 mm min 20 mm min 20 mm min 20 mm min 30 mm min 30 mm min 20 mm min 20 mm min 30 mm min 30 mm min 20 mm min 20 mm min 20 mm min 20 mm min 20 mm min 20 mm min 50 to 150 W Model Natural...

Page 4: ...ercurrent condition continued otherwise the internal elements of the S8PS may be dam aged or broken Overvoltage Protection The Power Supply is provided with an overvoltage protection func tion that pr...

Page 5: ...hing circuit Detector Control circuit Overload detection circuit Overload detection circuit Harmonic current control Smooth ing Overload detection circuit Overload detection circuit Rectifier smoothin...

Page 6: ...h 6 max Front mounting Bracket for 50 W Models Mounting Holes Using the Mounting Bracket Attach the Mounting Bracket to the panel and loosely tighten the two screws Insert the projected parts of the B...

Page 7: ...ounting Bracket for 100 150 W Models Dimensions with Mounting Bracket Using the Mounting Bracket S8PS 30024C 300 W Eight M4 depth 8 max also for the opposite side Mounting holes also on opposite side...

Page 8: ...our M4 depth 8 max 300 W models 600 W models Four M4 Four M4 10 dia Two 5 dia 600 W models Note Mount the Unit 21 6 mm away from the mounting surface in order to provide air ventilation on the rear si...

Page 9: ...y Unit when the Unit is shipped S8PS 10024D 100 W S8PS 10024CD 100 W S8PS 15024D 150 W S8PS 15024CD 150 W Five M4 terminal screws 3 5 dia 11 5 max 5 6 With slide 9 max Five M4 terminal screws 4 5 dia...

Page 10: ...Order Separately PFP 100N PFP 50N 4 5 15 25 25 25 25 10 10 1 000 500 see note 7 3 0 15 35 0 3 27 0 15 1 4 5 15 25 25 25 25 15 10 10 1 000 35 0 3 27 24 16 29 2 1 1 5 PFP 100N2 15 5 see note Note The va...

Page 11: ...been turned OFF Doing so may result in electric shock due to a residual voltage Do not touch the S8PS or heat radiation fin while the power is being supplied or immediately after the power is turned...

Page 12: ...dust As a preventive maintenance measure replace the fan within two years if it is used at an ambient temperature of 40 C Fans are available as replacements Model S82Y JFAN Fan Set Fan above four M4 x...

Reviews: