5 - 7
5 Maintenance and inspection
S8BA-series Uninterruptible Power Supply (UPS) User’s Manual (U726)
5
5
-2-2
P
rocedure for
replacing
the batter
y un
it
2
Pull out the cables from the old battery unit in the following order:
For details about the method of connecting cables to the terminal block, refer to
a cable to the battery terminal block, input terminal block and output terminal block
(1) Battery communication cable
(2) BATT connection cable
Negative side
(3) BATT connection cable
Positive side
3
Remove the old battery unit.
4
Install the new battery unit.