4 - 3
4 Operations
S8BA-series Uninterruptible Power Supply (UPS) User’s Manual (U726)
4
4
-1-1
LED display
: Steadily ON
: Blink
: OFF
Concept of LED display
No.
LED display
UPS
output
Charge
/Dis-
charge
Input
power
supply
Description
Procedures
[DC ON]
LED
(Green)
[BATT]
LED
(Yellow)
[ALERT]
LED
(Red)
1
OFF
---
OFF
No DC input.
Operation paused.
---
2
Blink 4
ON
Charge
ON
DC input.
Operating normally.
Charging.
---
3
ON
---
ON
DC input.
Operating normally.
---
4
ON
Dis-
charge
OFF
Backup operation due to
power failure or DC input
error. Output will stop if
backup operation is contin-
ued.
Process the termination of
the connected devices you
are using, and then stop the
devices.
5
Blink 1
ON
Dis-
charge
OFF
(Same as above)
Battery level is low, so out-
put will stop soon.
6
(*1)
(*2)
(*3)
Blink 0
ON
Charge/
Dis-
charge
ON/
OFF
Overpower detected (101%
or above) because connec-
tions exceeded capacity
limit (output continues).
Reduce connected devices
until the display condition
becomes as shown in No.3.
7
(*1)
(*2)
(*3)
Blink 0
OFF
Charge/
Dis-
charge
ON/
OFF
Output stopped due to the
detection of a short-circuit
on connected device side
or due to connections sig-
nificantly exceeding capac-
ity limit.
Check that the DC input of
connected devices is not
short-circuited, or that the
connection capacity does not
exceed the rated capacity.
8
Blink 4
(*1)
(*2)
OFF
---
ON
Output cannot be started
because the DC input volt-
age is outside the specified
range.
Note:
If this display occurs
when the unit has been
stopped by input of the
backup stop signal (BS)
(Page 7-2) or by using
the UPS monitoring soft-
ware (Page 6-2), the rem-
edy to the right is not
required because the
input voltage is within the
specification range.
Use in the DC input voltage
range described in the speci-
fication.
9
Blink 4
Blink 2
OFF
Charge
ON
Waiting to start up due to
low battery.
Continue charging the bat-
tery. When the set battery
level is reached, the UPS
automatically restarts.
10
Blink 0
Blink 0
ON
---
ON
Charging was stopped
because the ambient tem-
perature was detected as
55°C or above or 0°C or
below. (Displayed only
during normal operation.)
Ensure that the ambient tem-
perature is between 0°C and
55°C.
Summary of Contents for S8BA-24D24D480SBF
Page 5: ...Manual Structure 4 S8BA Series Uninterruptible Power Supply UPS User s Manual U726 ...
Page 21: ...Revision History 20 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...
Page 27: ...1 Overview of the product 1 6 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...
Page 55: ...4 Operations 4 10 S8BA series Uninterruptible Power Supply UPS User s Manual U726 ...