.Installation and connection
10
(3) For EIA standard-compliant installation, use the 8 included EIA rack
fi
xing nuts (M5) and 8
EIA/JIS rack
fi
xing screws (M5) to securely fasten the front (the side displaying “L” or “R”)
and the back of the support angles to the server rack.
③ The screw holes are located at
the top and bottom for both front and rear.
For JIS standards, use a total of 6 included screws to
fi
x the rack; 1 JIS rack
fi
fl
at-head
screw (M5) at a front position of the each of right and left support angles, 2 EIA/JIS rack
fi
x-
ing screws (M5) at 2 rear positions.
③
The screw hole position for the front is at the second
screw hole from the top, the rear is at the second screw hole from the bottom.
(4) Use the 8 included ear bracket mounting
fl
at-head screws (2 sets of 4 screws) to securely
fasten the ear brackets to the left and right sides of the UPS.
④
The support angles cannot be attached to special EIA/JIS racks.
(2) Adjust the length of support angles to suit the server rack, and then securely tighten the
screws that were half-tightened in step 1.
②
3
2
2
3
Rack fixing screws
Adjust the length to
suit the server rack
and tighten securely.
4
4