4
. UPS functions
32
ON
OFF
ON
OFF
ON
AC input
BS signal
Power supply
output
OFF
Power output stop delay time
This timing is 10 ms or 10 sec.
Timing corresponds to the settings
for switch
5
.
2) Power output stop delay time setting
It is possible to set the delay time for stopping the power supply output after the BS signal is
received. (Setting range: 0 to 10 minutes)
<Note>
The remote ON/OFF signal is not related to this setting.
When the remote ON/OFF signal is “ON”, the UPS stops the output immediately.
See also
→
Page 30
4-4-2. UPS operation mode settings
1. Settable items and explanations
There are three items to select.
1) Output voltage setting
2) Power output stop delay time setting
3) Signal input/output test
The settings available for this operation are shown below.
1) Output voltage setting (100V/110V/115V/120V)
Four types of output voltage can be set. (Setting range: 100V/110V/115V/120V)
Output is performed at the set voltage, with no relation to the input voltage.
See also
→
Page 35