background image

NXR-ILM08C-EIT

12

External Interface

Letter

Name

Function

(A)

EtherNet/IP communications 

connector 1

The connector for EtherNet/IP port 1.

• M12 connector (D-coding, female)

Connect a communications cable.

(B)

EtherNet/IP communications 

connector 2

The connector for EtherNet/IP port 2.

• M12 connector (D-coding, female)

Connect a communications cable.

(C)

I/O connectors

The connectors for connecting IO-Link devices or non-IO-Link connected external devices.

They are called "ports."

• M12 connectors (A-coding, female)

Connect I/O cables.

(D)

Power supply connector (input)

The connector for supplying Unit/input power and output power.

• 7/8 inch connector (male)

Connect the power supply cable to an external power supply.

(E)

Power supply connector (output)

The connector for supplying Unit/input power and output power from the local node to another 

node. Use this connector when the power supply method is power supply with through-wiring.

• 7/8 inch connector (female)

Connect the power supply cable to an additional IO-Link Master Unit.

(F)

I/O indicators

The indicators that show the I/O status of pin 4/pin 1 and pin 2 for each port.

(G)

Cover mounting holes

The screw holes for mounting the rotary switch cover. They are provided in two locations.

The above figure shows the holes when the cover is mounted with screws.

(H)

Rotary switches

The switches for setting the IP address.

(I)

Status indicators

The indicators that show the current operating status of the Unit.

(J)

Unit mounting holes

The holes for mounting the Unit. They are provided in two locations. Mount the Unit with M5 

screws.

(J)

(B)

(A)

(D)

(C)

(E)

(F)
(C)

(H)

(I)

(G)

(G)

(J)

Summary of Contents for NXR-ILM08C-EIT

Page 1: ...rnet cables Communication quality of EtherNet IP Records the total number of received FCS errors which allows checking communication quality Communication quality of IO Link Records the total number o...

Page 2: ...port Software for the Controller L Network Configurator C EtherNet IP adapter NXR series EtherNet IP IO Link Master Unit F IO Link device NXR series IO Link I O Hub G Non IO Link connected External De...

Page 3: ...ted external device is a sensor actuator or other device that handles ON OFF signals that are not supported by IO Link H Ethernet switch This is a relay device that connects multiple nodes I Communica...

Page 4: ...chine Automation Controller System Controller CJ series NJ NX series Software FA Integrated Tool Package CX One Automation Software Sysmac Studio Product name Specifications Model Number of licenses M...

Page 5: ...HARTING K K M12 plug D coding male to M12 plug D coding male 4 Screw connector Straight straight 0 5 m 72MDm4MDm4005K 1 m 72MDm4MDm4010K 2 m 72MDm4MDm4020K 3 m 72MDm4MDm4030K 5 m 72MDm4MDm4050K 10 m...

Page 6: ...d appearance Manufacturer Specification No of cable conductors Connector Cable connection direction Cable length Model XS3W Socket and Plug on Cable Ends M8 Socket M12 Plug OMRON M8 socket A coding fe...

Page 7: ...85 with no condensation Altitude 2 000 m max Pollution degree 3 or less Conforms to IEC 61010 2 201 Noise immunity 2 kV on power supply line Conforms to IEC 61000 4 4 Overvoltage category Category II...

Page 8: ...distance 100 m or less Distance between nodes and between hub and node Topology Line Star Tree Ring Number of connected Units Line Star No restrictions Tree There is no restrictions in the number of...

Page 9: ...ations connectors and I O connectors M12 screw 0 5 to 0 6 N m Power supply connectors 7 8 inch screw 1 5 to 1 7 N m Unit mounting M5 screw 1 47 to 1 96 N m Rotary switch cover M3 screw 0 4 to 0 6 N m...

Page 10: ...mum load current 2 A pin Leakage current 0 1 mA max Residual voltage 1 5 V max ON OFF response time 1 0 ms max Short circuit protection Provided 3 Short circuit detection Provided 3 Current consumptio...

Page 11: ...twork Configurator CX ConfiguratorFDT NXR ILM08C EIT Ver 1 1 Ver 1 14 Ver 2 1 Ver 1 40 Ver 3 69 Ver 2 54 Ver 1 0 IO Link Master Unit Corresponding versions Model Unit version CPU unit version CS1W EIP...

Page 12: ...supply E Power supply connector output The connector for supplying Unit input power and output power from the local node to another node Use this connector when the power supply method is power supply...

Page 13: ...NXR ILM08C EIT 13 Dimensions Unit mm 16 5 6 5 5 5 Two M5 or 5 3 dia holes Mounting dimensions 14 2 24 2 37 26 8 19 2 38 47 5 14 5 17 45 62 26 7 97 7 122 7 147 7 172 7 208 7 240 19 2 32 8 45 5 227 0 2...

Page 14: ...mple for an IO Link device with digital outputs for pin 2 is shown below In this example the port is used in the following communications modes Pin 4 IO Link Mode pin 2 SIO DI Mode Power supply connec...

Page 15: ...and outputs for pin 2 is shown below In this example the port is used in the following communications modes Pin 4 IO Link Mode pin 2 Disabled 4 2 3 1 2 1 3 4 2 1 3 4 U IN P U IN P Power supply connect...

Page 16: ...Sensors In this example the port is used in the following communications modes Pin 4 SIO DI Mode pin 2 Disabled Three wire sensor PNP type 4 2 3 1 2 1 3 4 U IN P U IN P Power supply connector input I...

Page 17: ...k output device is shown below In this example the port is used in the following communications modes Pin 4 SIO DO Mode pin 2 Disabled 4 2 3 1 2 1 3 4 U IN P Non IO Link output device U IN P OUT P OUT...

Page 18: ...Master Unit The power supply connector output is not used This method does not cause voltage drop in through wiring cables or due to connection through IO Link Master Units Unit input power supply Ou...

Page 19: ...he power supply connector input of another IO Link Master Unit with a power supply cable In this way supply power with through wiring between the subsequent Units with power supply cables The power su...

Page 20: ...NS communications Sysmac Studio Version 1 Operation Manual W504 SYSMAC SE2 Learning about the operating procedures and functions of the Sysmac Studio Describes the operating procedures of the Sysmac S...

Page 21: ...her in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity...

Reviews: