Reference
. .( $0&
Appendix E
Connecting an NT600S to an RS-232C/RS-422 Converter Unit (NT-AL001)
Connecting to an RS-232C/RS-422 converter unit allows transmissions over distances greater than 15 m (maxi-
mum of 500 m).
Max. 2 m
Max. 500 m
NT-AL001
Host
NT600S
RS-422A
RS-232C
When connecting a C200HX/HG/HE and an RS-232C/RS-422 converter unit, use
a converter unit whose lot number is 15Y5 or later. Converter units of lot numbers
previous to 15Y5 cannot be connected.
NT-AL001 RS-232C Connector Specifications (9-pin Type)
Electrical characteristics: Conform to EIA RS-232C
Signal direction: Signal input and output is relative to the NT-AL001.
Connector
Signal Name
Abbreviation
Signal Direction
Connector
Pin No.
Signal Name
Abbreviation
Input
Output
Connector cover
Grounding or earth for safety
purposes
FG
--
--
2
Send data
SD (TxD)
3
Receive data
RD (RxD)
4
Request to send
RS (RTS)
5
Clear to send
CS (CTS)
6
+5V input
+5V
9
Signal ground
SG (GND)
--
--
Summary of Contents for NT-series