3-6 Adjusting the Touch Panel and Display
3-6-1 Calibrating the Touch Panel
3-19
3
Installing th
e NSA-series Industria
l
PC and Con
necting Peripheral Devices
3-6 Adjusting the Touch Panel and
Display
3-6-1 Calibrating the Touch Panel
This section describes the procedure for calibrating the touch panel.
1. Calibrate the touch panel whenever it deviates markedly from its coordinate.
Connect a USB keyboard and mouse to the NSA-series Industrial PC before
calibrating the touch panel. Make sure the keyboard and mouse are properly
connected.
2. Start up the NSA-series Industrial PC and select Start – Programs – UPDD –
Settings from the bottom left corner of the screen to launch the settings
program.
3. Click the Calibration Tab on the Pointer Device Properties Menu, then click
the Calibrate Button.
Calibrate Button
Make sure the EEPROM
Calibration box is selected.
Settings