Setting the Rear Switches
•
I/O port selection (selector switch)
Set this to RS-232C.
•
Unit # (DIP SW1)
Set SW1-1 to SW1-5 to OFF (0).
•
Synchronization (selector switch)
Set this to Internal.
•
Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•
CTS selection (selector switch)
Set this always to 0 V (ON).
I/O port
Synchronization
Terminator
0 V
C1000H(F)/C2000H Rack-mounted type: C500-LK203
Setting the Rear Switches
•
I/O port selection (selector switch)
Set this to RS-232C.
•
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-7)
Set SW1-1 to SW1-7 to OFF (0).
•
Synchronization (selector switch)
Set this to Internal.
•
Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•
CTS selection (selector switch)
Set this always to 0 V (ON).
I/O port
Synchronization
Terminator
5V supply
0 V