![background image](http://html.mh-extra.com/html/omron/ns-rev-04/ns-rev-04_operation-manual_744516025.webp)
24
C1000H(F)/C2000H Rack-mounted Type: C500-LK203
Setting the Rear Switches
•
I/O port selection (selector switch)
Set this to RS-422A.
•
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-7)
Set SW1-1 to SW1-7 to OFF (0).
•
Synchronization (selector switch)
Set this to Internal.
•
Communications speed
(DIP SW2-1 to SW2-4)
Set these switches to 0010 to select
19,200 bps.
Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•
CTS selection (selector switch)
Set this always to 0 V (ON).
•
Terminator setting (selector switch)
Set this switch to ON.
I/O port
Synchronization
Terminator
5V supply
0 V
C200H/C1000H/C2000H CPU-mounted Type: C120-LK202-EV1
Setting the Rear Switches
•
Unit #, parity, and transfer code
(DIP SW1-1 to SW1-5)
Set SW1-1 to SW1-5 to OFF (0).
* Parity is fixed at Even Parity. Transfer code
is fixed at ASCII 7 data bits and 2 stop bits.
•
Communications speed (DIP SW2-1 to SW2-4)
Set these switches to 0010 to select 19200 bps.
Set these switches to 1010 to select 9600 bps.
(0: OFF 1: ON)
•
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to OFF (0) (1-to-N).
•
Command level (DIP SW2-7, SW2-8)
Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)
•
Terminator setting (DIP SW3-1 to SW3-6)
Set SW3-1, SW3-3, and SW3-5 to ON (1).
Set SW3-2, SW3-4, and SW3-6 to OFF (0).
(Set terminator ON.)