7
.
EtherNet/IP Connection Procedure
46
5
Enter
0040 4000
for
EIPOutput.CommandCode
in the
Modify
Column.
0040 4000 is displayed for
EIPOutput.CommandCode
in the
Online value
Column.
*The command code 0040 4000
(system data acquisition) is set.
6
In the same way as step 5, set
900
for
EIPOutput.Command
Param1
in the
Online value
Column.
*The system data number 900
(Number of digits displayed past
decimal point) is set.
7
Check that the online value of
EIPInput.SensorHeadStatusFlag1.F
[0]
is False. Click
TRUE
for
EIPOutput.SensorHeadControlFlag
1.F[0]
in the
Modify
Column.
True is displayed for
EIPOutput.SensorHeadControlFlag
1.F[0]
in the
Online value
Column,
and the command is executed.
When the command execution is
complete, True is displayed for
EIPInput.SensorHeadStatusFlag1.F
[0]
in the
Online value
Column.
8
When the process ends normally,
the online values of the response
variables are shown below.
EIPInput.CommandCodeEcho
:
0040 4000 (Execution
command code)
EIPInput.ResponseCode
: 0
(Command execution result
(0: OK, -1(FFFFFFFF): NG) is
reflected.)
EIPInput.ResponseData
: 1
(The number of digits displayed
past decimal point is 1. (Default))