![background image](http://html1.mh-extra.com/html/omron/ne1a-edr01/ne1a-edr01_operation-manual_743589099.webp)
82
Specifications and Dimensions
Appendix A
Note
In this case, pps means “packets per second” and indicates the number of packets that can be pro-
cessed in one second.
CIP Routing Specifications
Dimensions
Number of CIP connections
128
Allowable Module communica-
tions bandwidth
6,000 pps (See note.)
Explicit message communications Class 3 connection: Maximum message length of 502 bytes
UCMM connection: Maximum message length of 502 bytes
Item
Specifications
Port ID
EtherNet/IP: 2 (fixed)
DeviceNet: 3 (fixed)
Number of routing connections
16
Item
Specifications
(Unit: mm)
131.4
114.1
45.2
105.1
101.1