![background image](http://html1.mh-extra.com/html/omron/ne1a-edr01/ne1a-edr01_operation-manual_743589095.webp)
78
DST1 Series Monitoring
Section 4-7
(4) Instance ID
Status held in the DST1-XD0808SL-1 can be monitored by reading the
instance IDs shown in the following table.
Data (status) indicated by a black dot (
●
) can be read.
I/O Assembly Data
Format
Instance ID: 204
Monitor value: 1: ON, 0: OFF
Instance ID: 3A0
Monitor value: 1: ON, 0: OFF Operation result: 1: ON, 0: OFF
Instance ID: 3A1
Instance
ID (hex)
Safety
input
Safety
input
batch
status
Safety
input
status
Safety
output
batch
status
Safety
output
status
Muting
lamp
status
Safety
output
monitor
Test
output
status
Overall
status
204
●
3A0
●
●
●
3A1
●
●
●
●
●
●
●
●
●
Offset
(bytes)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
Safety input
terminal No.
7 monitor
Safety input
terminal No.
6 monitor
Safety input
terminal No.
5 monitor
Safety input
terminal No.
4 monitor
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
Offset
(bytes)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
Safety input
terminal No.
7 monitor
Safety input
terminal No.
6 monitor
Safety input
terminal No.
5 monitor
Safety input
terminal No.
4 monitor
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1
Reserved
Reset
request sig-
nal
Safety input
operation
result No. 5
Safety input
operation
result No. 4
(4/5)
Safety input
operation
result No. 3
Safety input
operation
result No. 2
(2/3)
Safety input
operation
result No. 1
Safety input
operation
result No. 0
(0/1)
Offset
(bytes)
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
+0
Safety input
terminal No.
7 monitor
Safety input
terminal No.
6 monitor
Safety input
terminal No.
5 monitor
Safety input
terminal No.
4 monitor
Safety input
terminal No.
3 monitor
Safety input
terminal No.
2 monitor
Safety input
terminal No.
1 monitor
Safety input
terminal No.
0 monitor
+1
Safety input
terminal No.
7 status
Safety input
terminal No.
6 status
Safety input
terminal No.
5 status
Safety input
terminal No.
4 status
Safety input
terminal No.
3 status
Safety input
terminal No.
2 status
Safety input
terminal No.
1 status
Safety input
terminal No.
0 status
+2
Safety out-
put termi-
nal No. 7
status
Safety out-
put termi-
nal No. 6
status
Safety out-
put termi-
nal No. 5
status
Safety out-
put termi-
nal No. 4
status
Safety out-
put termi-
nal No. 3
status
Safety out-
put termi-
nal No. 2
status
Safety out-
put termi-
nal No. 1
status
Safety out-
put termi-
nal No. 0
status
+3
Safety out-
put termi-
nal No. 7
monitor
Safety out-
put termi-
nal No. 6
monitor
Safety out-
put termi-
nal No. 5
monitor
Safety out-
put termi-
nal No. 4
monitor
Safety out-
put termi-
nal No. 3
monitor
Safety out-
put termi-
nal No.
2monitor
Safety out-
put termi-
nal No. 1
monitor
Safety out-
put termi-
nal No. 0
monitor
+4
Muting
lamp status
Reserved
Test output
terminal No.
3 status
Test output
terminal No.
2 status
Test output
terminal No.
1 status
Test output
terminal No.
0 status
Summary of Contents for NE1A-EDR01
Page 1: ...OPERATION MANUAL Cat No Z912 E1 01 NE1A Series NE1A EDR01 EtherNet IP DeviceNet Router...
Page 2: ...NE1A Series EtherNet IP DeviceNet Router NE1A EDR01 Operation Manual Produced July 2007...
Page 3: ...iv...
Page 7: ...viii TABLE OF CONTENTS...
Page 9: ...x...
Page 13: ...xiv...
Page 41: ...24 ED Router Settings Section 2 5...
Page 53: ...36 Error History Section 3 3...
Page 97: ...80 DST1 Series Monitoring Section 4 7...
Page 101: ...84 Settings from the Network Configurator Appendix B...
Page 105: ...88 Glossary...
Page 107: ...90 Revision History...