background image

2

Hermetically Sealed Relay 

MY4H

Specifications

Ratings

Coil

Contact Ratings

Characteristics

Rated voltage (V)

Rated current (mA)

Coil resistance 

(

)

Must operate 

voltage

Must release 

voltage

Max. voltage

Power 

consumption

50 Hz

60 Hz

DC

12

75

160

80% max.

10% min.

110%

900 mW

24

36.9

650

AC

110/120

9.9/10.8

8.4/9.2

4,430

30% min.

0.9-1.1 VA 
(60 Hz)

24

53.8

46

180

Contact material

Ag alloy

Rated load

Resistive 
p.f.=1

110 VAC, 3 A
24 VDC, 3 A

Inductive 
p.f.=0.4
L/R–7 ms

110 VAC, 8 A
24 VDC, 1.5 A

Rated carry current

3 A

Max. switching voltage

125 VAC, 125 VDC

Max. switching current

3 A

Max. switching power

330 VA
72 W

Contact resistance

50 m

 max.

Operate time

20 ms max.

Release time

20 ms max.

Max. operating 
frequency

Mechanical:

18,000 operations/hr

Electrical:

1,800 operations/hr (under rated load)

Insulation resistance

100 M

 min. (at 500 VDC)

Dielectric strength

1,000 VAC, 1 min between coil and contacts
1,000 VAC, 1 min between contacts of different polarity
700 VAC, 1 min between contacts of same polarity

Vibration resistance

Destruction:

10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)

Malfunction:

10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double amplitude)

Shock resistance

Destruction:

1,000 m/s

2

Malfunction:

When energized: 

200 m/s

2

When not energized: 

200 m/s

2

Endurance

Mechanical:

Single contact: 50,000,000 operations
Bifurcated contact: 5,000,000 operations

Electrical:

100,000 operations. (Single contact)
50,000 operations. (Bifurcated contact)

Ambient temperature

Operating:

–25 to 60

°

C

Ambient humidity

Operating:

5% to 85%

Weight

Approx. 50 g

Reviews: