Type: P9680

Type: P9680

Type: P9680

Type: P9680    & 

& P9680C

P9680C

P9680C

P9680C    

Combined Overcurrent and Earth Fault Relay

Combined Overcurrent and Earth Fault Relay

Combined Overcurrent and Earth Fault Relay

Combined Overcurrent and Earth Fault Relay    

 

 

True R.M.S. measurements 

 

Low Set and High Set tripping thresholds for both Overcurrent and Earth Fault detection 

 

6 selectable IDMT (Inverse Definite Minimum Time) characteristic curves  

 

Adjustable DT (Definitive Time)  

 

Three phase over current and earth fault detection with live display of individual phase and earth fault currents 

 

Last trip memory (last 10 trips stored and can be recalled) 

 

Pre-defined selectable CT ratio’s (5:5….6000:5) 

 

Microprocessor based (self-checking) with non-volatile memory 

 

“Ecosmart” Energy efficient power supply design 

 

Rear mounted pluggable connectors for supply, relay contacts and current inputs 

 

MODBUS-RTU version available (P9680C) 

 
      

 

  
  
 
                                                                                                                                                                                                                                                          
 
 
 

 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

OPERATION & OVERVIEW 

 

The 

P9680

P9680

P9680

P9680    

and 

P9680C

P9680C

P9680C

P9680C    

(from the P9600 series family of IDMT/DT relays) are microprocessor-

based relays designed to monitor and detect Overcurrent on individual phases and non-directional 
Earth faults (by measurement of the neutral current) in 3-phase applications. Typically, they

    

are wired 

in conjunction with external current transformers of the feeder to be protected. 

 

The 

P9680C 

P9680C 

P9680C 

P9680C 

model provides a MODBUS communication allowing the user access to settings, 

measurements and carry out a test and reset operation if required. Refer to the end of data sheet for 
further information. 

 

A clear backlit LCD provides all key information the user requires for both operation and setting up. 
Setting is achieved in a few simple steps and requires no previous knowledge of product operation. 

 

Normal operation provides the user with actual live individual phase currents and earth fault current 
all on one screen. The actual phase current represents that of the current passing through the 
primary side of the externally connected CT’s. This is achieved by the setting of the ratio for the CT.  

 

Programming mode allows the user to assign the operation mode for both internal relays. They can 
be individually assigned to Overcurrent, Earth fault or a combination of both. They can also be 
configured for Auto or Manual resetting. Relay 2 has the added option of being allowed to energise 
at the start or end of a time out period. If assigned to energise at the start, the Relay can be used to 
operate a buzzer or lamp giving early warning before a system actually shuts down. 

 

Low-set and High-set thresholds can be programmed for both Overcurrent and Earth fault 
detection. The time current characteristic of the low-set units are selectable between Normal 
Inverse curve 3/10, Normal Inverse curve 1.3/10, Long Time Inverse curve, Very Inverse curve, 
Extremely Inverse curve, Extremely Inverse 0.65 curve and Definite Time. High-set units are the 
Definitive Time type. Instantaneous tripping is possible by setting the time to minimum. 

 

Two simple Summary screens are displayed once the programming is complete. The same screens 
can also be displayed by presses of the 

“RESET” 

button. This allows the user to access key 

information with the tamperproof transparent cover closed and sealed. 

 

A Test mode is provided (also accessible with tamperproof transparent cover closed) to confirm the 
correct operation of the internal relays. The relays will energise when the 

“TEST”

 button is pressed 

and de-energise when the button is released (AUTO Reset) or when the 

“RESET”

 button is pressed 

(MAN Reset). 

 

Following a trip condition, the information about the trip is then stored. This can then be recalled 
later if required using the 

“RESET” 

button to access the information. The 

P9680/P9680C

P9680/P9680C

P9680/P9680C

P9680/P9680C

 have the 

ability to store up to 10 trips and using the “Up” and “Down” buttons, allows each trip to be 
displayed individually. Each trip is also marked with a time stamp showing the time from power up as 
well as the time from the previous trip. This feature is very useful for establishing a pattern on 
particular inputs, knowing when they occurred and how frequent! 
 

 

FUNCTION OVERVIEW 

 

Programming mode. 

 
 
 
 
 
 
 
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
              
 
 
 

Programmable parameters            P9680C only 

 

 
User settings summary mode 
 
 
 
 
 
 

 
 
 
 

1

 Summary screens are split into two with one screen showing Overcurrent settings and the 

other showing Earth fault settings. 

2

 Displaying of the Summary screens during normal operation is achieved via subsequent 

presses of the “RESET” button. See Section 8. QUICK VIEW OF USER SETTINGS 
for further information. 

 

PRESENTATION

 

 

 

 
 

 

    

    

    

    
    
    
    
    

    

1. LCD (Liquid Crystal Display) for user information     5. 

“MODE” 

button* 

2. 

“RESET”

 button                                   6. Parameter increment button* 

3. 

“TEST”

 button                                    7. Parameter decrement button* 

4. 

“Power supply”

 green LED indication               8. 

“Trip status” 

red LED indication 

                                                     

* accessible only when the front cover is open 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START 

TOROID RATIO 

Set ratio of externally 

connected toroids

 

 

NETWORK 

FREQUENCY 

Set for 50 or 60Hz 

connected toroids

 

RELAY 1 SETTING 

Assign monitoring function 

and set reset mode method 

RELAY 2 SETTING 

Assign monitoring function, 

relay activation and reset 

mode methods 

OVERCURRENT 

SETTING 

Set Low-set and High-set 

tripping parameters 

EARTH FAULT 

CURRENT SETTING 

Set Low-set and High-set 

tripping parameters 

 

SUMMARY

1

 

List all parameter and 

function settings

 

 

START 

Display live individual 

phase currents and 

earth fault current 

SUMMARY

1 2

 

List all parameter and 

function settings

 

Dims: 

W x H. 96 x 96mm (front) 

W x H. 89.5 x 89.5mm (main body) 

L. 100mm 

 

I

L1

 

0.00

A

 

I

L2

 

0.00

A

 

I

L3

 

0.00

A     

 

I

  

0.00

A     

 

 

 

 

MODBUS 

SETTINGS 

Configure address, baud 

and parity 

 

 

Summary of Contents for P9680C

Page 1: ...iving early warning before a system actually shuts down Low set and High set thresholds can be programmed for both Overcurrent and Earth fault detection The time current characteristic of the low set...

Page 2: ...occurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9680 P9680 P96...

Page 3: ...fers to Overcurrent and E F refers to Earth fault PROGRAMMING continued Press and hold the button to set the options for Relay 2 Relay 2 Relay 2 Relay 2 as described in the next section 3 RELAY 2 SETT...

Page 4: ...further button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8...

Page 5: ...been cleared The LCD reverts back to displaying the normal system currents and the red Tripped Tripped Tripped Tripped LED stops flashing If either relay is set for Auto resetting then they would hav...

Page 6: ...0 05 t t t t s s s s 10 1 0 1 0 01 t t t t s s s s Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 NI 3 10 NI 3 10 NI 3 10 NI 3 10 t t t t s s s s k k k k 1 0 0 9 0 8...

Page 7: ...tch female connector supplied with unit Recommended wiring type 2 core shield twisted pair 24AWG i e Belden type 9841NH TECHNICAL SPECIFICATION Aux Supply voltage Un 1 2 85 265VAC 85 370VDC1 18 55VAC...

Page 8: ...is as follows Address 1 Address 2 Address n Modbus Master The P9680C is provided with a Modbus termination switch It is recommended that for the last unit connected in the system the switch is set to...

Reviews: