background image

 

  

 

 

 
 

 
 
 
 
 

 

 

 

 
 

 

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: [email protected] Web: www.broycecontrol.com

 

The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk

P9640-3-A

  1

1

1

1    

XXXXXX 

 

 

 

 

  

Type: P964

Type: P964

Type: P964

Type: P9640

0

0

0    

1.3/10 or 3/10

1.3/10 or 3/10

1.3/10 or 3/10

1.3/10 or 3/10

^

^

^

^

    

Inverse 

Inverse 

Inverse 

Inverse Definite

Definite

Definite

Definite Minimum

 Minimum

 Minimum

 Minimum Time (

 Time (

 Time (

 Time (IIIID

D

D

DM

M

M

MT)

T)

T)

T) Earth Fault Relay

 Earth Fault Relay

 Earth Fault Relay

 Earth Fault Relay    

 

 

True R.M.S. measurements 

 

Adjustable Low-set and High-set tripping threshold (with option to disable High-set tripping) 

 

Adjustable Time Multiplier for defining curve tripping characteristic (applicable to Low-set triggering only) 

 

Normal Inverse 1.3/10 or 3/10 tripping characteristics (Low-set threshold only)^ 

 

Instantaneous tripping on High-set triggering 

 

Test and Reset button for simulating and clearing of fault condition 

 

Red LED indication of Low-set or High-set triggering and tripping 

 

Green LED indication for Auxiliary power supply presence 

 

Microprocessor based (self checking) with non-volatile memory 

 

Terminals suitable for 2 x 2.5mm

2

 wires (complete with protective cover) 

^ 1.3/10 or 3/10 must be specified at time of ordering 

 
 
      

 

  
  
 
                                                                                                                                                                                                                         
 
 
 

 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 

 

GENERAL OVERVIEW 

 
The P9640 (from the P9600 series family of IDMT/DT relays) is a microprocessor based relay 
designed to monitor and detect Earth faults in 3-phase applications. Typically the P9640 is 
wired in conjunction with external current transformers of the feeder to be protected. 
 
The P9640 can be supplied with either a Normal Inverse 1.3/10 or Normal Inverse 3/10 
tripping curve. This should be specified at the time of ordering. Either version is clearly marked 
at both the front and rear of the product. 
 
The adjustments and indicators are laid out to help the user during set-up and fault finding. 
The adjustment for the Low

Low

Low

Low----set

set

set

set for example has its corresponding red LED positioned above 

it so it is clear to which function this LED relates to. The same also applies to the High

High

High

High----set

set

set

set 

adjustment and LED. Adjustment and LED operation is explained further on the next page. 
 
The adjustment for TM (k) 

TM (k) 

TM (k) 

TM (k) (which defines the curve response to tripping)    is assigned to the 

Low

Low

Low

Low----set

set

set

set triggering only. The High

High

High

High----set

set

set

set does not have any additional adjustments and hence will 

trip instantaneously if triggered. If required, the High

High

High

High----set

set

set

set can be set to disabled. 

 
A Test mode is provided (also accessible with the tamperproof transparent cover closed) to 
confirm the correct operation of the internal relay. The relay will energise when the “TEST” 

“TEST” 

“TEST” 

“TEST” 

button is pressed and de-energise when the “RESET”

“RESET”

“RESET”

“RESET” button is pressed. 

 
 
 
 

 

 
 
 
 
 

 
 
 

 

OPERATION 

 

Example 1. 

 

  When an Overcurrent occurs in one of the phases and the level of 
current exceeds the “L

“L

“L

“Low

ow

ow

ow----set

set

set

set Io>”

 Io>”

 Io>”

 Io>” trip threshold, the corresponding 

red LED above the adjustment illuminates. The time out then 
commences however the point at which tripping occurs is defined by: 

 

A, the level of current that is above the trip threshold. 
B, the Time Multiplier setting. 

 

When tripping finally occurs, the red LED will then flash indicating a 

tripped condition. 
 
  If the fault current has been removed, pressing the ““““RESET”

RESET”

RESET”

RESET” button 

will return the relay back to normal operation. The red LED will then 
extinguish. 

 

Example 2. 

 

If a fault current occurs such that it exceeds the “High

“High

“High

“High----set Io

set Io

set Io

set Io>>”

>>”

>>”

>>” trip 

threshold the relay will de-energise with no delay. The red LED above 
the ““““High

High

High

High----set Io

set Io

set Io

set Io>>”

>>”

>>”

>>” adjustment will flash. 

 

In the event of an Earth fault condition, the basic sequence of 
events is shown below. 

Assuming High-set trip is enabled.

 

    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    
    

 

PRESENTATION

 

 

 

 
 

 

    

    

    

    
    
    
    
    

 

  

 

    
    
    
    
    
    
    
    
    
    
    
    
    
    

1.  

“Time Multiplier”

 adjustment*                     5. 

“Low-set triggered” 

red LED indication 

2. 

“Low-set Io>”

 trip adjustment*                    6. 

“High-set triggered” 

red LED indication 

3. 

“High-set Io>>”

 trip adjustment*                  7. 

“TEST”

 button   

4. 

“Power supply”

 green LED indication               8. 

“RESET”

 button       

                                                      * accessible only when the front cover is open 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START 

EARTH FAULT 

occurs 

Low-set I

o

triggered

 

Time out 

commences 

High-set 

I

o

>> 

triggered? 

TRIP! 

 
 
 

Time out 
complete 

‰

 

 

Dims: 

W x H. 96 x 96mm (front) 

W x H. 89.5 x 89.5mm (main body) 

L. 107mm 

 

 

Reviews: