K8AK-TH

4

Connections

Wiring Diagrams

Timing Charts

Power supply 
voltage*

1

Power supply 
voltage*

1

Power supply

Relay output

Power supply

Relay output

External input
(LATCH_RST)

*

2

Sensor input

External input 
(LATCH_RST)

*

2

Sensor input

Not used. 

Not used. 

Not used. 

Thermocouple

Thermocouple

Pt resistance thermometer input

1

+

2

3

4

5

6

14 11 12

A1

A2

1

+

2

3

4

5

6

14 11 12

A1

A2

A

B

B

Not used. 

Not used. 

K8AK-TH11S

K8AK-TH12S

*1 The input power supply depends on the 

model: 100 to 240 VAC or 24 VAC/VDC (no 
polarity)

*2

Wiring of the external input terminals is as shown 
below.

Relay output (normally closed) (11) to (14)

Relay output (normally open) (11) to (14)

Temperature alarm or other error

Power supply

Relay output (latched) (11) to (14)

LATCH_RST or external inputs (4) to (5)

Temperature alarm or other error

Power supply

PWR indicator

SV Protect Mode

Power supply

ALM indicator

Temperature alarm

Power supply

Other error

Temperature alarm lower limit (11) to (14)

Temperature alarm upper limit (11) to (14)

Temperature setting

0.02 s

2°C (°F)

2°C (°F)

Flashing

Flashing

Temperature Alarm: Hysteresis: 2°C/°F

Changing between Normally Open and Normally Closed

Latched Operation: Relay outputs remain latched even after the alarm 
or error is reset.

Operation of Indicators

* To enter SV Protect Mode or reset the latch, turn ON the LATCH_RST signal or 

external input for at least 5 seconds.

* Other errors: sensor open circuit error, sensor input error, temperature setting 

error, and memory error.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Summary of Contents for K8AK-TH

Page 1: ...or the setting ranges Note When ordering designate the power supply specification Different Relay models are used for 100 to 240 VAC and 24 VAC VDC Refer to Safety Precautions on page 8 For the most r...

Page 2: ...30 VDC Maximum switching capacity 1 250 VA 150 W Minimum load 5 VDC 10 mA reference values Mechanical life 10 million operations min Electrical life 5 A at 250 VAC or 30 VDC 50 000 operations 3 A at...

Page 3: ...setting increment 10 C Input K J T E B R S PLII Setting temperature range 3 200 3 100 3 000 2 900 2 800 2 700 2 600 2 500 2 400 2 300 2 200 2 100 2 000 1 900 1 800 1 700 1 600 1 500 1 400 1 300 1 200...

Page 4: ...ther error Power supply Relay output latched 11 to 14 LATCH_RST or external inputs 4 to 5 Temperature alarm or other error Power supply PWR indicator SV Protect Mode Power supply ALM indicator Tempera...

Page 5: ...e than one million times If you press and hold the LATCH_RST button for 5 seconds or longer the SV Protect Mode will go into effect When SV Protect Mode is enabled the PWR indicator flashes To disable...

Page 6: ...ult All OFF SW8 Not used R_SW3 K8AK TH12S R_SW2 R_SW1 SW 1 2 3 4 K 5 6 7 J T E B R S PLII Input type ON OFF 100 C F units 0 to 9 10 C F units 0 to 9 Upper limit alarm Lower limit alarm With latching W...

Page 7: ...ated The protection function can be released by pressing the output latch reset button on the Temperature Monitoring Relay for at least 5 s or by turning ON the input to the external input terminal fo...

Page 8: ...he side panel take effect when the power is turned ON If the Temperature Monitoring Relay fails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities eq...

Page 9: ...ring Relay to stabilize Take this time into account when you design the control panel 14 Allow at least 30 minutes for the product to warm up During this time the temperature measurements will be inco...

Reviews: