K8AK-AW

7

Timing Charts

• Always turn on the control power supply for K8AK at least 2 seconds before load startup.
• Be aware that there is a power ON lock time (approx. 1 s) for the K8AK.
• Output relays 11-14 and 21-24 will be conductive when the input level is normal.
• The startup lock time only functions during the first load startup. After load is stopped, the startup lock time will be in effect again when restarted.
• There is no startup lock time function when monitoring undercurrent.

Overcurrent and Undercurrent Operation Diagram (Overcurrent/Undercurrent Monitoring Mode)

DIP switch settings: SW3 ON and SW4 ON, or SW3 OFF and SW4 OFF

Overcurrent and Overcurrent Operation Diagram (Overcurrent/Overcurrent Monitoring Mode) 
(When Using as an Overcurrent Pre-alarm)

DIP switch settings: SW3 ON and SW4 OFF

Note: 1. The K8AK-AW

 output contacts are normally operative.

 

2. Power ON lock prevents unnecessary alarms from being generated during the unstable period when the power is first turned ON.

 

  There is no contact output during timer operation.

 

3. There is no startup lock time function for monitoring undercurrent.

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

K8AK power supply voltage

Power ON

Undercurrent (AL2)

contacts (21-24)

Undercurrent set value (AL2)
30% of AL1 current set value

Overcurrent (AL1)

contacts (11-14)

Lit

AL2 alarm indicator

AL1 alarm indicator

Overcurrent set value (AL1)

Lit

Flashing

Flashing

Power ON lock (approx. 1 s)

Delay: 250 ms
(reference value)

Delay: 250 ms
(reference value)

Delay: 250 ms
(reference value)

Delay: 250 ms
(reference value)

Input

Operating time

(0.1 to 30 s)

Operating time
(0.1 to 30 s)

Operating time
(0.1 to 30 s)

Startup lock time
(0 to 30 s)

Startup lock time
(0 to 30 s)

Lit

Flashing

0 A

See note 3.

Note: 1. The K8AK-AW

 output contacts are normally operative.

 

2. Power ON lock prevents unnecessary alarms from being generated during the unstable period when the power is first turned ON.

 

  There is no contact output during timer operation.

Flashing

Lit

Flashing

Lit

Hysteresis: Fixed at 5%

Hysteresis: Fixed at 5%

AL1 alarm indicator

AL2 alarm indicator

Overcurrent (AL1)

contacts (11-14)

Overcurrent set value (AL2)

30% of AL1 current set value

30% of AL2 current set value

Overcurrent (AL2)

contacts (21-24)

Overcurrent set value (AL1)

0 A

K8AK power supply voltage

t: Operating time (0.1 to 30 s)

t: Operating time (0.1 to 30 s)

t

t

Delay: 250 ms
(reference value)

Delay: 250 ms
(reference value)

Delay: 250 ms
(reference value)

Power ON lock (approx. 1 s)

AL1 startup lock time
(0 to 30 s)

AL2 startup lock time
(0 to 30 s)

Summary of Contents for K8AK-AS1 24VAC/DC

Page 1: ...ent Transformer CT Direct input is not possible Accessory Order Separately OMRON CT Commercially Available CTs If you use a commercially available CT do not exceed the overload capacity of the K8AK AW...

Page 2: ...mA AC DC 50 to 500 mA AC DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 0 to 100 mA AC DC I2 COM Approx 1 Direct input 0 to 500 mA AC DC I3 COM Approx 0 2 Direct input K...

Page 3: ...puts ALM Red Input impedance Refer to Input Range on previous page Output relays Two SPDT relay outputs normally closed operation Output relay ratings Rated load Resistive load 5 A at 250 VAC 5 A at 3...

Page 4: ...minals Between input terminals and output terminals Dielectric strength 2 000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals Between power su...

Page 5: ...h the OMRON K8AC CT200L Current Transformer CT Wiring Example Directly Inputting a Current Using a CT Always turn on the control power supply for the K8AK at least 2 seconds before turning on the powe...

Page 6: ...AL1 Contact b for the approx 1 second interval immediately after the K8AK control power supply is turned on After that a switch to contact a will be made as an overcurrent state is no longer present A...

Page 7: ...K8AK power supply voltage Power ON Undercurrent AL2 contacts 21 24 Undercurrent set value AL2 30 of AL1 current set value Overcurrent AL1 contacts 11 14 Lit AL2 alarm indicator AL1 alarm indicator Ove...

Page 8: ...ng time 0 1 to 30 s t Operating time 0 1 to 30 s t t Delay 250 ms reference value Delay 250 ms reference value Delay 250 ms reference value Delay 250 ms reference value Flashing Flashing Power ON lock...

Page 9: ...ched the same level Use this as a guide to set the current The maximum setting range will differ depending on the model and the input terminal Example K8AK AW3 Using Input Terminals I3 COM The maximum...

Page 10: ...de to set the startup lock time The startup lock time will start when the input current reaches 30 or more of the set value Use startup lock time to prevent unwanted operation e g as a result of inrus...

Page 11: ...figure for information on the motor startup current For a motor with a rating of 5 A the startup current will be approximately 30 A The startup current will exceed the overload capacity rating 150 for...

Page 12: ...cified torque of 0 49 to 0 59 N m Use of the product beyond its life may result in contact welding or burning Make sure to consider the actual operating conditions and use the product within its rated...

Page 13: ...ifficult to see 15 Do not use the product if it is accidentally dropped The internal components may be damaged 16 Be sure you understand the contents of this catalog and handle the product according t...

Page 14: ...MEMO 14...

Page 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 16: ...0169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com...

Reviews: