background image

K3HB-X

4

Input Range (Measurement Range and Accuracy) CAT II

Note: 1.

The accuracy is for an input frequency range of 40 Hz to 1 kHz (except for AD current input A and B ranges of 50 to 60 Hz) and an ambient
temperature of 23 ±5

°

C. The error, however, increases below 10% of the maximum input value.

DC voltage input (all ranges): 10% or less of max. input = ±0.15% FS
DC current input (all ranges): 10% or less of max. input = ±0.1% FS
AC voltage input (A: 0.0 to 400.0 V): 10% or less of max. input = ±0.15% FS
AC voltage input (B: 0.00 to 199.99 V): 10% or less of max. input = ±0.2% FS
AC voltage input (C: 0.000 to 19.999 V; D: 0.0000 to 1.9999 V): 10% or less of max. input = ±1.0% FS
AC current input (A: 0.000 to 10.000 A): 10% or less of max. input = ±0.25% FS
AC current input (B: 0.0000 to 1.9999 A): 10% or less of max. input = ±0.5% FS
AC current input (C: 0.00 to 199.99 mA; D: 0.000 to 19.999 A): 10% or less of max. input = ±0.15% FS
When DC voltage input models are used with a ±1.9999 V range, make sure that the connections between input terminals are not open.
If the input terminals are open, the display will show large variations. Connect resistance of approximately 1 M

Ω

 between the input ter-

minals if they are open. 

2.

The letters “rdg” mean “reading” and refer to the input error.

3.

The value (0.5 VA CT) is the VA consumption of the internal CT (current transformer). 

4.

The K3HB-XVA

@@

 complies with UL standards when the applied input voltage is within the range 0 to 150 VAC.

If the input voltage is higher than 150 VAC, install an external transformer or take other measures to drop the voltage to 150 VAC or lower.

Input type

Range

Set value

Measurement range

Maximum 

measurement range

Input 

impedance

Accuracy

Allowable 

instantaneous 

overload (30 s)

K3HB-XVD 
DC voltage

A

a Ud

±199.99 V

-199.99 to 219.99 V

10 M

Ω 

min.

±0.1%rdg  ± 1 
digit max.

±400 V

B

b Ud

±19.999 V

-19.999 to 21.999 V

1 M

Ω 

min.

±200 V

C

c Ud

±1.9999 V

-1.9999 to 2.1999 V

D

d Ud

1.0000 to 5.0000 V

0.5000 to 5.5000 V

K3HB-XAD
DC current

A

a ad

±199.99 mA

199.99 to 219.99 mA

Ω 

max.

±0.1%rdg  ± 1 
digit max.

±400 mA

B

b ad

±19.999 mA

19.999 to 21.999 mA

10 

Ω 

max.

±200 mA

C

c ad

±1.9999 mA

1.9999 to 2.1999 mA

33 

Ω 

max.

D

d ad

4.000 to 20.000 mA

2.000 to 22.000 mA

10 

Ω 

max.

K3HB-XVA
AC voltage 
(See note 4.)

A

a Ua

0.0 to 400.0 V

0.0 to 440.0 V

1 M

Ω 

min.

±0.3%rdg  ± 5 
digits max.

700 V

B

b Ua

0.00 to 199.99 V

0.00 to 219.99 V

C

c Ua

0.000 to 19.999 V

0.000 to 21.999 V

±0.5%rdg  ± 10 
digits max.

400 V

D

d Ua

0.0000 to 1.9999 V

0.0000 to 1.9999 V

K3HB-XAA
AC current

A

a aa

0.000 to 10.000 A

0.000 to 11.000 A

(0.5 VA CT)
(See note 3.)

±0.5%rdg  ± 20 
digits max.

20 A

B

b aa

0.0000 to 1.9999 A

0.0000 to 2.1999 A

(0.5 VA CT)
(See note 3.)

C

c aa

0.00 to 199.99 mA

0.00 to 219.99m A

Ω 

max.

±0.5%rdg  ± 10 
digits max.

2 A

D

d aa

0.000 to 19.999 mA

0.000 to 21.999m A

10 

Ω 

max.

COM

+

±

1.9999 

V

1 M

Ω

E2

E3

E4

E5

E6

Summary of Contents for K3HB-X

Page 1: ...1 L1A Linear current output 0 to 20 or 4 to 20 mA DC Sensor power supply 12 VDC 10 80 mA See note 2 L2A Linear voltage output 0 to 5 1 to 5 or 0 to 10 VDC Sensor power supply 12 VDC 10 80 mA See note...

Page 2: ...tup compensa tion timer input NPN open collector or no voltage contact signal ON residual voltage 2 V max ON current at 0 4 mA max Max applied voltage 30 VDC max OFF leakage current 0 1 mA max Hold in...

Page 3: ...m s2 for relay outputs 3 times each in 3 axes 6 directions Weight Approx 300 g Base Unit only Degree of protection Front panel Conforms to NEMA 4X for indoor use equivalent to IP66 Rear case IP20 Term...

Page 4: ...nal CT current transformer 4 The K3HB XVA complies with UL standards when the applied input voltage is within the range 0 to 150 VAC If the input voltage is higher than 150 VAC install an external tra...

Page 5: ...at 250 VAC 5 A at 30 VDC 1 A at 250 VAC 1 A at 30 VDC Mechanical life expectancy 5 000 000 operations Electrical life expectancy 100 000 operations Maximum load voltage 24 VDC Maximum load current 50...

Page 6: ...ne Communications distance Baud rate Network length max Drop line length max Total drop line length max 500 Kbps 100 m 100 m 6 m 39 m 250 Kbps 100 m 250 m 6 m 78 m 125 Kbps 100 m 500 m 6 m 156 m The v...

Page 7: ...yed Used to switch level Used to switch the display between the PV maximum value and minimum value and to reset the maximum and minimum values PV display SV display Position meter SV display status in...

Page 8: ...ote Leave 20 ms min between DATA VALID turning OFF and the REQUEST signal See note See note See note Programmable Controller Connection Example Digital Indicator SYSMAC Programmable Controller DC Inpu...

Page 9: ...C 80 mA 12 VDC 80 mA 10 VDC 100 mA 10 VDC 100 mA Sensor power supply communications Sensor power supply Sensor power supply K33 CPB K33 CPA K33 B K33 A K33 L2B K33 L1B K33 L2A K33 L1A RS 485 K33 FLK3B...

Page 10: ...re also available E Analog Input D Event Input D6 3 9 k 4 7 k S TMR D2 HOLD D3 RESET D4 ZERO D5 12 V COM D6 D1 750 560 TIMING 12 V COM Models with Terminal Blocks K35 1 K35 3 Models with Connectors K3...

Page 11: ...atus Turns the comparative output OFF until the measurement value enters the PASS range Average processing of input signals with extreme changes or noise smooths out the display and makes control stab...

Page 12: ...r red to green The current display value can be selected from the present value the maximum value and the minimum value It is possible to specify i e restrict the values that the smallest dis played d...

Page 13: ...Higher Lower Output HH Output PASS Output H Output L Output LL Measurement value Higher Lower Measurement value Higher Lower Comparative set value HH Comparative set value H Comparative set value L C...

Page 14: ...cutout in the panel 2 Insert watertight packing around the Unit to make the mounting watertight 3 Insert the fixture into the grooves on the left and right sides of the rear case and push until it rea...

Page 15: ...turn OFF the power 19 Use the specified cables for the communications lines and stay within the specified DeviceNet communications distances Refer to the User s Manual Cat No N129 for details on comm...

Page 16: ...e running lines along separate ducts and using shield lines Example of Countermeasures for Inductive Noise on Input Lines 4 If a noise filter is used for the power supply check the voltage and current...

Page 17: ...ther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity...

Reviews: