13
K3HB-C
■
Dimensions
Wiring Precautions
•
For terminal blocks, use the crimp terminals suitable for M3 screws.
•
Tighten the terminal screws to the recommended tightening torque
of approx. 0.5 N·m.
•
To prevent inductive noise, separate the wiring for signal lines from
that for power lines.
Wiring
• Use the crimp terminals suitable for M3 screws shown below.
Unit Stickers (included)
•
No unit stickers are attached to the Digital Indicator.
•
Select the appropriate units from the unit sticker sheets provided.
Mounting Method
1.
Insert the K3HB into the mounting cutout in the panel.
2.
Insert watertight packing around the Unit to make the mounting
watertight.
3.
Insert the adapter into the grooves on the left and right sides of
the rear case and push until it reaches the panel and is fixed in
place.
LCD Field of Vision
The K3HB is designed to have the best visibility at the angles shown
in the following diagram.
Character Size for Main Display (mm)
Terminal: M3, Terminal Co
v
er: Accessory
Terminal co
v
er (incl
u
ded)
PV display
SV display
14.2
4.9
3.5
7.6
96
48
1.3
12
(112)
100
101.2
91
2
44.8
Panel C
u
to
u
t Dimensions
45
+0.6
0
92
+0.8
0
75 min.
*
1. De
v
ice
N
et models: 97 mm
*
2. Lea
v
e a distance of at least 140 mm
w
hen
u
sing the Wate
Co
v
er Y92A-49
N
.
95
*
1
120 min.
*
2
Note:
Mo
u
nting Recommended Panel Thickness
1 to 8 mm.
Mo
u
nt the prod
u
ct horizontally.
Note:
For measurements for commercial purposes, be sure to use
the unit required by any applicable laws or regulations.
5.8 mm max.
5.8 mm max.
Watertight
packing
Adaptor
10
°
30
°
Watertight Cover
Y92A-49N
Rubber Packing
K32-P1
If the rubber packing is lost or damaged, it can be ordered
using the following model number: K32-P1.
(Depending on the operating environment, deterioration, con-
traction, or hardening of the rubber packing may occur and so,
in order to ensure the level of waterproofing specified in
NEMA4, periodic replacement is recommended.)
Note:
Rubber packing is provided with the Controller.