CHAPTER3 COMMUNICATIONS DATA
H8GN
3-2
3.1 Variable Area (setup range) List
The following table lists the variable areas. Items expressed in hexadeciĆ
mal in the Set (monitor) Value" column are the setting range. Values in
parentheses ()" are the actual setting range.
For details of variable areas that are described not in numerical values but
by text, refer to the relevant parameter descriptions.
Variable
type
Address
Item
Set (monitor) Value
Level
C0
0000
Version * Note 1
H'00000100
C0
0001
PV
H'FFFFFC19 to H'0000270F (-999 to 9999)
* Counter
* At PV underflow,
lower limit value=H'FFFFFC19 (-999)
Operation
H'00000000 to H'0000270F (0 to 9999)
* Time range at timer=other than Ć ĆmĆ Ćs, Ć ĆhĆ Ćm
H'00000000 to H'000026E7 (0:00 to 99:59)
* Time range at timer=Ć ĆmĆ Ćs, Ć ĆhĆ Ćm
C0
0002
Status * Note 1
See 3.2. Status."
C0
0003
Totalizing count value
H'00000000 to H'05F5E0FF (0 to 99999999)
Operation
C1
0000
Operation/adjustment
protection
H'00000000 (0): No restrictions in operation and adĆ
justment levels
H'00000001 (1): Move to adjustment level restricted
H'00000002 (2): Display and change of only PV/SV
parameters enabled
H'00000003 (3): Display of only PV/SV parameters
enabled
Protect
C1
0001
Initial setting/commuĆ
nications protection
H'00000000 (0): Move to initial setting/communicaĆ
tions setting level enabled (move to
advanced function setting level disĆ
played)
H'00000001 (1): Move to initial setting/communicaĆ
tions setting level enabled (move to
advanced function setting level not
displayed)
H'00000002 (2): Move to initial setting/communicaĆ
tions setting level restricted
C1
0002
Setting change protecĆ
tion
H'00000000 (0): OFF (changing of setup on controlĆ
ler display enabled)
H'00000001 (1): ON (changing of setup on controller
display disabled)
C1
0003
Reset key protection
H'00000000 (0): OFF (reset key enabled)
H'00000001 (1): ON (reset key disabled)