background image

H8BM

H8BM

12

Example of Input Connections (Solid-state Switches)

Two-wire Sensors
The count input, counter No. select input, reset input, I/O inhibit in-
put, and re-monitor input signals are enabled when voltage is ap-
plied.

Two-wire sensor

IN COM

All inputs

H8BM

24 VDC

Two-wire sensor

All inputs

IN COM

H8BM

24 VDC

Note:

Use the following two-wire sensors:

1. High-level; transistor ON

Min. switching capacity: 5 mA max.
Residual voltage: 4 V max.

2. Low-level: transistor OFF

Leakage current: 1.5 mA max.

3. Power voltage range: 20.4 to 30 VDC

Use of the OMRON TL-XD or E2E-XD-N Sensors is recommended.

Three-wire Sensors

NPN Type

PNP Type

Main
sensor
circuit

All inputs

COM

H8BM

Main
sensor
circuit

All inputs

COM

H8BM

Main
sensor
circuit

COM

All inputs

H8BM

Main
sensor
circuit

COM

All inputs

H8BM

Contact Switch Connection

COM

All inputs

H8BM

All inputs

COM

H8BM

*H: Contact ON.
*Use contact that can break 13 mA, 30 V

Summary of Contents for H8BM Series

Page 1: ...C sensors RC Ordering Information Number of stages Output Model 3 stage setting NPN H8BM B 3 s age se g PNP H8BM BP 1 stage setting NPN H8BM BD s age se g PNP H8BD BDP Accessories Order Separately Rep...

Page 2: ...Note 1 Each channel operates on an separate I O 2 Pre forecast Displayed only on LCD No external output is provided Forecast Displayed on LCD and LED and output Output for each Counter Machine stoppa...

Page 3: ...ck generator LCD reference voltage generator Key switch circuits Input circuits count 1 to 9 reset re monitor output number request I O inhibit Count circuits One chip microcomputer LCD Output circuit...

Page 4: ...TER No Key Selects the Counter in sequence each time this Selector is pressed Any Counter whose forecast value is set to 0 is skipped in the RUN mode The following indicators light to show that the co...

Page 5: ...e Indication Forecast Value Setting Mode Indication Pre forecast Value Setting Mode Indication Flashing Machine Stoppage Value Setting Mode Indication Flashing Note 1 The modes marked are not provided...

Page 6: ...is time the count value is only displayed and not recovered internally The Counter whose count value is displayed remains in the RUN mode 2 Press the COUNTER No Key or apply the Counter No select inpu...

Page 7: ...e of only the Counter whose count value is cur rently displayed is reset in RUN mode only 9 Clearing Settings The count values of all the Counters can be cleared by simultaneously holding down the RES...

Page 8: ...ime value Pre forecast indicator Forecast output and indicator Machine stoppage output and indicator Totalizing Counter Operation Reset input Count input 999999 0 Count value Forecast output indicator...

Page 9: ...en mounting it to en sure a proper working space Other components Terminal Arrangement 22 23 24 25 26 27 28 Reset input Count No selection Count input 1 Count input 2 Count input 3 Count input 4 Count...

Page 10: ...recast output 5 Forecast output 6 Forecast output 7 Forecast output 8 Forecast output 9 Machine stoppage output RUN output OUTPUT COM 24 V 0 V 24 VDC 10 15 5 V Power circuit Load Load Load Load Load L...

Page 11: ...d Load Load Load Load Load Load Load OUTPUT COM Note H8BM BD BDP outputs the forecast and machine stoppage values simultaneously OUTCOM 30 VDC Max Load All outputs Connect a diode to suppress Counter...

Page 12: ...1 High level transistor ON Min switching capacity 5 mA max Residual voltage 4 V max 2 Low level transistor OFF Leakage current 1 5 mA max 3 Power voltage range 20 4 to 30 VDC Use of the OMRON TL XD o...

Page 13: ...nner as well as strong acids or strong alkalies can damage the housing of the Counter Others To conduct a dielectric strength test between the electric circuits and non current carrying metal parts wi...

Reviews: