background image

 

EMC-D3b 

EMC-D3b-485 

instructon manual 

IM450-U v3.1 

page 1 

 

INSTRUCTION MANUAL 

IM450-U v3.1

 

 

EMC-D3b

 

ENERGY MULTIFUNCTION COUNTER

 

EMC-D3b-485

 

 
AVAILABLE MODELS 
EMC-D3b

: 3-phase energy counter with 7+1 digit display. 1 digital 

input and two digital pulse output for kWhr and kVArhr. 

EMC-D3b-485

: 3-phase energy counter with 7+1 digit display, 1 

digital input, two digital pulse output for kWhr and kVArhr, EIA-
RS485 serial communication port, Modbus RTU protocol. 
Both are manufactured in DIN rail mounting case 6 modules 17.5 
mm. 
 

INTRODUCTION 

The EMC-D3b models allows the local or remote counting of the 
energy, with the help of a serial interface. 
It is possible to set the instrument to count in 3 differents mode 
(Normal / Total and partial / Timeband). 
Also the instrument is equipped with a digital input which can cover differents function. See the 

digital input

 

section for 

more information. 
The auxiliary power supply is taken from same Voltage inputs (VL1 and VL2), used for measuring. 
It’s available as option the instrument for single phase networks. 

 
 

OPTIONS and ACCESSORIES 
options

: - internal CT's ( 

not for direct line insertion

) (order with -t suffix) 

- current inputs for ... /1A current transformer (order with /1A suffix) 
- current sensor for low current measures (Max 15 Amp) (specify when ordering) 
- power supply and measuring voltages other than the standard (specify when ordering) 
- power supply separated from measuring voltage (specify when ordering) 
- single phase network ( power supply is taken from VL1 and neutral) (specify when ordering) 

 

MEASURED PARAMETERS 

Parameters showed in counter mode 

Unit of measure  

Identifying abbreviations 

three phase system active energy  

[kWhr] 

kWh 

three phase system reactive energy  

[kVArhr] 

kVArh 

three phase system apparent energy 

[kVAhr] 

kVAh 

Parameters showed in meter mode 

unit of measurement 

initial identification 

phase voltages 

[V-kV] 

L1-N

 V 

L2-N

 V 

L3-N

 

 

phase to phase system voltages 

[V-kV] 

L1-L2

 V 

L2-L3

 V 

L3-L1

 

 

phase currents 

[A-kA] 

L1

 A 

L2

 A 

L3

 

 

phase power factors 

 

PF 

L1

 PF 

L2

 PF 

L3

 

 

phase active powers 

[W-kW-MW] 

L1

 W 

L2

 W 

L3

 

 

phase reactive powers 

[VAr-kVAr-MVAr] 

VAr 

L1

 VAr 

L2

 VAr 

L3

 

 

phase apparent powers 

[VA-kVA-MVA] 

VA 

L1

 VA 

L2

 VA 

L3

 

 

frequency [Hz] 

Hz 

L1

 

 

 

 

 
These parameters are available only on EMC-D3b-485 model and readable only by RS485 interface.

 

Peak, average and max demand value  

unit of measurement 

Initial identification 

maximum phase voltages 

[V-kV] 

L1-N max

 V 

L2-N max

 V 

L3-N max

 

maximum phase currents 

[A-kA] 

L1

 

max

 A 

L2 max

 A 

L3 max

 

maximum three-phase powers 

[W-VAr-VA (k-M)] 

 W 

max

 

 VAr 

max

 

 VA 

max

 

maximum average phase currents (maximum demand) 

[A-kA] 

L1 max (avg)

 I 

L2 max (avg)

 I 

L3 max (avg)

 

maximum average three-phase powers (maximum demand)  [W-VAr-VA (k-M)] 

 W 

max (avg)

 

 VAr 

max (avg)

 

 VA 

max (avg)

 

average phase currents 

[A-kA] 

L1

 

avg

 A 

L2 avg

 A 

L3 avg

 

average three-phase powers 

[W-VAr-VA (k-M)] 

 W 

avg

 

 VAr 

avg

 

 VA 

avg

 

Summary of Contents for EMC-D3b

Page 1: ...other than the standard specify when ordering power supply separated from measuring voltage specify when ordering single phase network power supply is taken from VL1 and neutral specify when ordering...

Page 2: ...nd authorised staff must carry out maintenance and or repair Should it be considered that there is a safety loss during operation the instrument must be disconnected and precautions taken against acci...

Page 3: ...ust not overcome 500 Vrms depending always on the instrument s power supply In case of three phase application with or without neutral not distributed it is enough not to connect the terminal N The tr...

Page 4: ...INSERTION ON THREE PHASE LINE WITH 4 WIRES AND 3 VT BALANCED THREE PHASE LINE LOAD P1 P1 P1 P2 S1 S1 S1 S2 N L1 L2 L3 S2 S2 S2 S1 S1 S1 I1 I2 I3 VL1 VL2 VL3 N measure cu rren t inputs measure vo ltag...

Page 5: ...erred at the L1 phase The others data displayed relatives at value of three phase system are not to consider VL1 VL2 VL3 N EMC measure vol tage in puts LOAD S2 S2 S2 S1 S1 S1 I1 I2 I3 measure cu rren...

Page 6: ...he energy counting is being accumulated on time band 2 F LED indicating energy counting The frequency of blinking is proportional to the energy displayed G LED for indication of reactive energy counti...

Page 7: ...L1 PUL 10 0 kW kVAr pulse Set pulse weight 01 0 kW kVAr pulse 00 1 kW kVAr pulse 0 01 kW kVAr pulse TPL 100 mS Set the duration pulse 200 mS 300 mS 400 mS 500 mS only for EMC D3b 485 ID Increase Set...

Page 8: ...RMAL Only one counter is available for each energy resetting the energies is available only by the front panel E TOT PAR Two counters are available for each energy the total counters are not resettabl...

Page 9: ...he instrument when it will be connected in a EIA485 communication network proceed with the modality already described The settable values are from 1 to 247 To confirm press the C key Programming of th...

Page 10: ...CHED OFF SWITCHED OFF SWITCHED OFF SWITCHED ON Energy operating mode TIME BAND Parameter LED s STATUS LED kWh LED kVARh LED T1 LED T2 Visualisation active energy T1time band Energy counting on T1 time...

Page 11: ...POWER FACTOR PHASE L3 PF3 000 ACTIVE POWER PHASE L1 PL1 000 ACTIVE POWER PHASE L2 PL2 000 ACTIVE POWER PHASE L3 PL3 000 REACTIVE POWER PHASE L1 QL1 000 REACTIVE POWER PHASE L2 QL2 000 REACTIVE POWER...

Page 12: ...80 Vac to 250 Vac 50 60Hz From 90 Vdc to 300Vcc polarised Serial output Only for EMC D3b 485 one RS485 port 2400 to 19200 baud s MODBUS RTU protocol GENERAL Display operation keys 1 display with red...