24-hour/Weekly Time Switch

 H2F

7

Manual Switch

SPST-NO Output

A 3-position selector switch, located at the lower left corner of the
front panel, determines output operation. In the OFF position, the
control output is forcibly turned OFF regardless of the setting of the
programming tabs. Set to the AUTO position, the output is turned ON
and OFF according to the settings of the programing tabs. In the ON
position, the output is forcibly turned ON regardless of the setting of
the programming tabs.

SPDT Output

When the manual switch at the lower left corner of the front is set to
the OFF position, both load 1 (connected across terminals 4 and 5)
and load 2 (across 5 and 6) are turned OFF.

When it is set to the AUTO position, the output is turned ON and OFF
according to the setting of the programming tabs.

When the manual switch is set to the ON position, load 1 (connected
across terminals 4 and 5) is turned ON and load 2 (across 5 and 6) is
turned OFF.

Output Indicator

The output indicator at the upper left corner of the front panel shows
the status of the output when the manual switch is set to the AUTO
position.

In addition, the output can be manually turned ON or OFF by rotating
the knob clockwise (in the arrow direction). The knob will not turn
counterclockwise.

Precaution for the H2F-D, -DF Series (Synchronous Motor 
Models)

Before using the H2F, select the appropriate frequency of your area
by the frequency selector switch provided on the upper part of the
rear panel.

H2F-

@

M Series (Quartz Motor Models)

Battery

Remove the battery cover on the rear panel of the H2F, load the pro-
vided Battery into the battery box, then turn ON the H2F. Be sure to
load the Battery before using the H2F. If the Battery is not loaded, the
H2F will not work properly.

Be sure to load the Battery with the correct polarity. The polarity is
indicated in the battery box. After loading the Battery, be sure to
place the cover on the battery box.

The Battery is fully charged before shipment. The Battery may lose
its charge while the Battery is stored. Therefore, there is a backup
function that is guaranteed for 180 hours on condition that the Bat-
tery is loaded into the H2F and charged continuously for 72 hours. If
the Battery has no charge, the H2F may not operate immediately
after it is turned ON. In that case, continue providing power to the
H2F for three or more minutes before setting the time.

If the H2F is turned ON and OFF frequently, the Battery life will be
greatly reduced. Use the H2F with a continuous supply of power.

The Battery has a life of approximately three years at room tempera-
ture. If three years have passed since the Battery was loaded,
replace the Battery as soon as possible with a AAAA-size NiCd
rechargeable battery.

If the H2F is idle over a long time, unload the Battery from the H2F
and store the Battery separately in order to prevent the Battery from
being overly discharged.

Always turn OFF the power supply before replacing the Battery. 

Use only the specified Replacement Battery (Y92S-42). Using any
other battery may result in leakage of battery fluid or battery rupture,
possibly causing equipment damage or injury. 

Other Precautions

When connecting to a heater, always use a thermal switch in the load
circuit. 

Do not exceed the specified ranges for vibration and shock. 

The H2F is neither waterproof nor oil-proof. Do not use the H2F
where it would be subjected to water or oil. 

Upper part of rear panel 
(cycles per second)

Press down.

Battery cover

Slide out

Battery

Summary of Contents for H2F -

Page 1: ...ntrol outputs Minute dial assures accurate settings Models with memory protection available Control outputs can be manually turned ON OFF Designed for surface flush or track mounting Model Number Structure Model Number Legend 1 Operation cycle D 24 hour W 1 week 2 Motor type None Synchronous motor M Quartz motor 3 Mounting method None Flush mounting F Surface mounting DIN track mounting 4 Output t...

Page 2: ...tz motor with memory protection Flush SPST NO H2F D H2F DM H2F WM SPDT H2F DC H2F DMC H2F WMC Surface track SPST NO H2F DF H2F DMF H2F WMF SPDT H2F DFC H2F DMFC H2F WMFC Extra Programming Tabs 1 pair for each ON OFF See note 1 Y92S 21 Rechargeable Battery See note 2 Y92S 42 Operation period Minimum division Minimum set time Maximum set time 24 hour 15 min 15 min 23 h 45 min 1 week 1 h 2 h 166 h Op...

Page 3: ...ax Memory protection against power failure 180 h min See note 3 Insulation resistance 100 MΩ min at 500 VDC Dielectric strength 2 000 VAC 50 60 Hz for 1 min between current carrying terminals and non current carrying metal parts 1 000 VAC 50 60 Hz for 1 min between non continuous contacts Vibration resistance Destruction 16 7 Hz 2 mm single amplitude Malfunction 10 to 55 Hz 0 25 mm single amplitud...

Page 4: ...to the load 2 Do not exceed the following torque when tightening the screws Specified torque 0 8 N m Maximum torque 0 98 N m 3 When connecting leads to the terminal block use the same wire size for all leads If different wire sizes are used the thinner leads may come off during operation 4 Recommended lead wires AWG18 to AWG24 cross section 0 205 to 0 823 mm2 solid or twisted wire 5 When using cri...

Page 5: ...ated Mounting Dimensions Surface Mounting H2F DF DMF WMF Track Mounting H2F DFC DMFC WMFC Mounting Holes M3 5 6 29 Two M3 holes Screw size M3 x 45 included Flush Mounting H2F D DM WM DC DMC WMC Panel Cutout Recommended panel thickness 1 to 3 2 mm Note The mounting adapter and screws are included 65 5 ...

Page 6: ...Time Setting To set the time turn the center knob clockwise to the correct time Turning it counterclockwise or turning it with your fingers hooked on the setting bracket may cause a malfunction With 24 hour models set the hour to the arrow on the upper left cor ner of the front panel and the minute to the arrow on the center knob With 1 week models set the day of the week to the arrow on the upper...

Page 7: ...F Be sure to load the Battery before using the H2F If the Battery is not loaded the H2F will not work properly Be sure to load the Battery with the correct polarity The polarity is indicated in the battery box After loading the Battery be sure to place the cover on the battery box The Battery is fully charged before shipment The Battery may lose its charge while the Battery is stored Therefore the...

Page 8: ...of the terminals or the back panel while power is being supplied Doing so may result in electric shock Be sure to mount the terminal cover after wiring Before changing times or other settings while power is being supplied either turn OFF the power on the load side or set the output ON OFF switch to OFF and confirm the safety of the system Unexpected operation may occasionally result Tighten the te...

Reviews: