7
D40A/G9SX-NS
Ratings (Non-contact Door Switch Controllers)
Power input
*
Power consumption of loads not included.
Inputs
*1.
Only applies to the G9SX-NSA222-T03-
@
. Refers to input other than that from the Non-contact Door Switch.
*2.
Provide a current equal to or higher than that of the minimum applicable load of the connected input control device.
Outputs
*1.
While safety outputs are in the ON state, the following signal sequence is output continuously for diagnosis.
When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below.
*2.
The following derating is required when Units are mounted side-by-side.
G9SX-NS202-
@
/G9SX-NSA222-T03-
@
: 0.4 A max. load current
Expansion Unit
Item
Model
G9SX-NS202-
@
G9SX-NSA222-T03-
@
G9SX-EX-
@
Rated supply voltage
24 V DC
Operating voltage range
−
15% to 10% of rated supply voltage
Rated power consumption
*
3 W max.
4 W max.
2 W max.
Item
Model
G9SX-NS202-
@
/G9SX-NSA222-T03-
@
Safety input
*1
Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8 k
Ω
*
2
Feedback/reset input
Item
Model
G9SX-NS202-
@
/G9SX-NSA222-T03-
@
Instantaneous safety output
*
1
OFF-delayed safety output
*
1
P channel MOS FET transistor output
Load current: 0.8 A DC max.
*
2
Auxiliary output
PNP transistor output
Load current: 100 mA max.
O
N
OFF
360
μ
s max.
Approx.100 ms
Item
Model
G9SX-EX-
@
Rated load
250 VAC, 3 A/30 VDC, 3 A (resistive load)
Rated carry current
3 A
Maximum switching voltage