G9SP
Function Support by Unit Version of G9SP
Serial communication speed
*
The baud rate can be set to 115,200 bps with turning on the DIP swith pin 3.
Connectivity with OMRON safety input devices
Programmable Terminal NB series
Programmable Terminals
Software
*
NB-Designer version 1.32 or later can be used with G9SP.
For detail, refer to the NB Series catalog (Cat. No. V412-E1).
Item
Unit Version
Ver.1.
@
Ver.2.0
Communications protocol
No-protocol
Communication speed
9,600 bps
9,600 bps
115,200 bps
*
Transmission disutance
max.15 m
max.15 m
(With a baud rate of 115,200 bps: max.3 m)
Data length
8 bits
Parity
Even
Stop bits
1 bit
Item
Unit Version
Ver.1.
@
Ver.2.0
Single-beam Safety Sensor
E3ZS, E3FS
max.1 unit
G9SP-N10D/N20S: max.6 units
G9SP-N10S
: max.4 units
Non-contact Door Switche
D40A, D40Z
G9SP-N10D/N20S: max.30 units
G9SP-N10S
: max.15 units
Safety Mat
UM
max.12 units
Product name
Specifications
Model
NB3Q
3.5 inch, TFT LCD, Color, 320
×
240 dots
NB3Q-TW00B
3.5 inch, TFT LCD, Color, 320
×
240 dots,
USB Host, Ethernet
NB3Q-TW01B
NB5Q
5.6 inch, TFT LCD, Color, 320
×
234 dots
NB5Q-TW00B
5.6 inch, TFT LCD, Color, 320
×
234 dots,
USB Host, Ethernet
NB5Q-TW01B
NB7W
7 inch, TFT LCD, Color, 800
×
480 dots
NB7W-TW00B
7 inch, TFT LCD, Color, 800
×
480 dots,
USB Host, Ethernet
NB7W-TW01B
NB10W
10.1 inch, TFT LCD, Color, 800
×
480 dots,
USB Host, Ethernet
NB10W-TW01B
Product name
Specifications
Support Software for NB Series
NB-Designer
*
Supported Operating Systems:
Windows 10, Windows 8.1, Windows 8, Windows 7, Windows Vista ,
Windows XP (SP3 or higher).
Note:
Note: Except for Windows XP 64-bit version
Download from Omron's regional websites.
®