Power Relays
G7Z
5
Ordering Information
■
Relay with Auxiliary Contact
Block
Relay with Auxiliary Contact Block
(for Screw Terminals)
■
Accessories (Order Separately)
Auxiliary Contact Block
Specifications
■
Ratings
Coil Ratings
Note: 1. Rated current and coil resistance were measured at a coil temperature of 23
°
C with coil resistance of
±
15%.
2. Operating characteristics were measured at a coil temperature of 23
°
C.
3. The maximum allowable voltage is the maximum value of the fluctuation range for the Relay coil operating power supply and was measured at an ambient
temperature of 23
°
C.
There is, however, no continuous allowance.
Contact Ratings
Relay
Note: The ratings for the auxiliary contact block mounted on the G7Z are the
same as those for the G73Z auxiliary contact block.
Auxiliary Contact Block
Contact configuration
Rated voltage
Model
Relay
Auxiliary contact
block
4PST-NO
DPST-NO
12, 24 VDC
G7Z-4A-20Z
SPST-NO/SPST-NC 12, 24 VDC
G7Z-4A-11Z
DPST-NC
12, 24 VDC
G7Z-4A-02Z
3PST-NO/
SPST-NC
DPST-NO
12, 24 VDC
G7Z-3A1B-20Z
SPST-NO/SPST-NC 12, 24 VDC
G7Z-3A1B-11Z
DPST-NC
12, 24 VDC
G7Z-3A1B-02Z
DPST-NO/
DPST-NC
DPST-NO
12, 24 VDC
G7Z-2A2B-20Z
SPST-NO/SPST-NC 12, 24 VDC
G7Z-2A2B-11Z
DPST-NC
12, 24 VDC
G7Z-2A2B-02Z
Contact
configuration
Model
DPST-NO
G73Z-20Z
SPST-NO/SPST-NC G73Z-11Z
DPST-NC
G73Z-02Z
Item
Rated current
Coil resistance
Must operate
voltage
Must release
voltage
Maximum
voltage
Power
consumption
Rated voltage
Percentage of rated voltage
12 VDC
333 mA
39
Ω
75% max.
10% min.
110%
Approx. 3.7 W
24 VDC
154 mA
156
Ω
Model
G7Z-4A-
@
Z, G7Z-3A1B-
@
Z,
G7Z-2A2B-
@
Z
Item
Load
Resistive
load
Inductive
load cos
φ
=
0.3
Resistive
load L/R = 1
ms
Contact structure
Double break
Contact material
Ag alloy
Rated load
NO
40 A at
440 VAC
22 A at
440 VAC
5 A at
110 VDC
NC
25 A at
440 VAC
10 A at
440 VAC
5 A at
110 VDC
Rated carry current
NO
40 A
22 A
5 A
NC
25 A
10 A
5 A
Maximum contact voltage
480 VAC
125 VDC
Maximum contact
current
NO
40 A
NC
25 A
Maximum switching
capacity
NO
17,600 VA
9,680 VA
550 W
NC
11,000 VA
4,400 VA
550 W
Failure rate P value (reference
value)
2 A at 24 VDC
Model
G73Z-20Z, G73Z-11Z, G73Z-02Z
Item
Load
Resistive
load
Inductive
load cos
φ
=
0.3
Resistive
load L/R = 1
ms
Contact structure
Double break
Contact material
Au clad + Ag
Rated load
1 A at
440 VAC
0.5 A at
440 VAC
5 A at
110 VDC
Rated carry current
1 A
Maximum contact voltage
480 VAC
125 VDC
Maximum contact current
1 A
Maximum switching capacity
440 VA
220 VA
110 W
Failure rate P value (reference
value)
1 mA at 5 VDC