background image

88

Power Controllers 

G3PX

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. K076-E1-04

• The Level indicator is not OFF with a 0% input signal (G3PX-

2

@

0EUN Series).

Make sure that the BASE UP adjuster has been turned counter-
clockwise to the minimum setting.

• The OPEN indicator of a multiple heater open circuit detection 

model is lit at the initial stage (G3PX-2

@

0EHN Series).

Make sure that the initial settings are OK. If not, readjust the 
G3PX.
Make sure that terminals 18 and 19 are open if the supply 
frequency is 50 Hz. These terminals must be short-circuited if the 
supply frequency is 60 Hz.

Make sure that the load current is large enough.

• The Level indicator LEDs of a constant-current model are all lit and 

no power control operation is possible.

Make sure that the load current is large enough.

Countermeasure 1: Adjust the CUR LIM adjuster so that the LED 
on the farthest right of the Level indicator is OFF.

Countermeasure 2: When the supply current is less than 50%, 
increase the number of turns. When the supply current is 50% of 
the rated current, the wires must be coiled twice on the CT Unit. 
When the supply current is 25% of the rated current, the wires 
must be coiled three to four times on the CT Unit.

• No reset will be performed even if the RESET button is pressed. 

Check whether the RESET button is pressed while there is nothing 
input into to power supply terminals 8 and 10 or 9 and 10 of the 
G3PX.

Be sure to press the RESET button with power supplied to the 
G3PX.

The following wiring will be required if the breaker or contactor 
connected between the power supply and the G3PX is operated 
by the relay output of the G3PX.

BASE UP

Make sure that the 
adjuster is turned 
counterclockwise to the 
minimum setting.

Adjust so that this LED is OFF.

CUR LIM adjuster for limiting current

Load

Magnet 
contactor

Summary of Contents for G3PX

Page 1: ...and Incorporating Overcurrent Detecting and Single Heater Open Circuit Detecting Functions OMRON s unique design and carefully selected materials made it possible to produce a compact and lightweight...

Page 2: ...X Accessory for G3PX 2 Basic Model Name CT CT Unit 3 Length of Lead Wires 03 30 cm 10 100 cm 4 Series Blank Series for single heater open circuit detection HN Series for multiple heater open circuit d...

Page 3: ...h of the lead wires by adding a code to the model number as shown below G3PX 2 0EC CT03 CT with 30 cm long lead wires G3PX 2 0EC CT10 CT with 100 cm long lead wires 2 When ordering make sure that the...

Page 4: ...2 EHN G32X CT03HN 100 cm G32X CT10HN 30 cm G3PX 2 EC G32X CT03C 100 cm G32X CT10C Name Carry current Applicable models Model Power Device Cartridge 20 A G3PX 220E G32X A20 40 A G3PX 240E G32X A40 60 A...

Page 5: ...ange 0 to 95 Internal duty setting range 0 to 100 10 to 100 See note 1 0 to 100 External duty setting range 0 to 100 10 to 100 See note 1 0 to 100 Start up time See note 2 Approx 0 5 to 10 s See note...

Page 6: ...330 A within 1 cycle Constant current 3 max with 10 time increment of load value 3 max with 10 change of voltage Abnormality detection time 1 s max Voltage drop with output ON 1 6 V max RMS Leakage cu...

Page 7: ...100 60 40 20 G3PX EUN EH EHN Models Output voltage Input current mA G3PX EC Models G3PX EUN EH EHN Models Output voltage Input current mA 100 60 40 20 Output voltage Input current mA G3PX 2 0EUN Model...

Page 8: ...ent A Peak Inrush current A Peak G3PX 220E Models Energized time ms G3PX 240E Models G3PX 260E Models Energized time ms Energized time ms Note The above are possible on condition that the G3PX is in n...

Page 9: ...r Device Cartridge TIME adjuster for extended soft start time DUTY adjuster for internal slope setting ALARM adjuster for multiple heater open circuit detection OPEN indicator for multiple heater open...

Page 10: ...tinue operating with level indication 2 When EH EHN EC series models detect a short mode failure the SHORT indicator is lit and the SPDT relay output is ON Note When the G3PX detects a short mode fail...

Page 11: ...or the G3PX and the load Load 1 Load 2 Load 200 230 VAC 100 110 VAC 1 2 3 4 5 6 7 8 9 10 G3PX 250 4 5 G3PX 4 5 250 G3PX 600 Load 1 Load 2 4 to 20 mA 4 to 20 mA Impedance Note Two G3PX models can be co...

Page 12: ...ications No of G3PX E5 K 40 mA at 12 V 20 sets E5 N 20 mA at 12 V 20 sets 20 mA at 5 V 20 sets 10 mA at 5 V 20 sets 1 2 3 4 5 6 7 8 9 10 3 2 1 G3PX Load 1 Load 2 DUTY Note You can change the duty with...

Page 13: ...OPEN indicator is lit Stop turning the ALARM adjuster as soon as the indicator is lit to complete the setting 3 2 1 G3PX 1 2 3 4 5 6 7 8 9 10 3 2 1 Load 1 Load 2 DUTY G32X V3K or G32X V2K External DU...

Page 14: ...g as the controlled phase is approximately 1 6 or more in width 2 Be sure to prepare terminals 18 and 19 corresponding to the supply frequency of 50 Hz or 60 Hz Otherwise a setting error will result i...

Page 15: ...on the indented portions of the Power Device Cartridge as shown in the illustration below and pull up the Power Device Cartridge vertically Mounting The procedures for mounting the Power Device Cartr...

Page 16: ...nter screws of the G3PX with a tightening torque of 0 59 to 0 78 N m 6 Attach the terminal cover 7 Switch on the power and check the G3PX to be sure it works properly External Variable Resistor The G3...

Page 17: ...6 8 6 140 0 2 50 0 2 130 119 108 120 13 13 109 8 140 0 2 65 0 2 130 140 0 3 50 0 3 7 6 7 6 G3PX 220E Series G3PX 240E Series Mounting Holes Two M4 screws 70 max 130 max 150 max 130 max 65 0 2 85 max...

Page 18: ...0 2 50 30 9 5 24 35 14 55 40 17 G32X CT03 Series G32X CT10 Series Mounting Holes Two 4 5 dia or M4 holes 60 max see note 2 17 dia hole 15 dia see note 1 Note 1 Color of the hole EH Series Black EHN Se...

Page 19: ...input VOLTAGE IN Current input 4 to 20 mA DC CURRENT External duty setting 3 k B MAN DUTY SET 200 230 VAC 50 60 Hz 100 110 VAC 50 60 Hz 2 k B 2 W for EUN series models Internal contact configuration E...

Page 20: ...model 1 47 N m 40 A model 2 45 N m 60 A model 4 12 N m Terminal block Single phase model 0 98 N m Be sure to protect the terminals with the protective cover after wiring Wiring for Error Detection If...

Page 21: ...e Models Only Do not apply 200 V to the 100 V terminals otherwise the thermal fuse of the built in transformer will be blown and the G3PX will not operate Others It is not possible to use three single...

Page 22: ...no power control operation is possible Make sure that the load current is large enough Countermeasure 1 Adjust the CUR LIM adjuster so that the LED on the farthest right of the Level indicator is OFF...

Reviews: