76

Power Controllers 

G3PX

Operation

Error Detecting Function

Wiring

Single-phase Models

All G3PX-2

@

0EH/EHN/EC-series models incorporate terminals 11 

and 12 for the CT Unit, 13 and 14 for the external reset switch, and 
16 and 17 for relay output as well as power/input terminals 1 through 
10.

Output

Single-phase Models

The following illustrations show the condition of the G3PX LED 
indicators when the G3PX detects heater open circuit, a short-mode 
failure (ON failure of components), or overcurrent (EC-series 
constant-current models only). The indicator and relay output signals 
are reset with the internal or external reset switch provided that the 
error condition has been remedied.

1. When EH/EHN/EC-series models detect single or multiple heater 

open circuit, the OPEN indicator is lit and the SPDT relay output 
is ON.

Note: When the G3PX detects heater open circuit, the Level indicator 

will be OFF regardless of the G3PX input condition. The red 
OPEN indicator will be lit. EHN-series models, however, will 
continue operating with level indication.

2. When EH/EHN/EC-series models detect a short-mode failure, the 

SHORT indicator is lit and the SPDT relay output is ON.

Note: When the G3PX detects a short-mode failure, all LEDs of the 

Level indicator and red SHORT indicator are lit. When you use 
a breaker to disconnect the load with the relay output, all LEDs 
of the Level indicator will be OFF regardless of the input to the 
G3PX.

3. When EC-series models detect an overcurrent, the Level 

indicator will flash and the SPDT relay output is ON. The input 
signal will be shut off.

Note: When resetting, leave power supply terminals 10 to 9 or 8 ON.

11

12

13

14

15

16

17

G3PX-2

@

0EH

CT Unit
G32X-CT

@@

   3.   For more than one heater.

Load 1

Load 2

CT Unit

Relay output 
(SPDT)

Load

(see note 1)

(see note 2)

(see note 3)

External reset 
switch

Note:   1.   Connect either the black or white lead wire of the CT 

Unit to terminal 11 and the other lead wire to terminal 
12. The G3PX will malfunction if you do not connect 
the CT Unit to the G3PX.

   2.   The rated current and voltage of G3PX models when 

reset are as follows:

 

EH-series models: 12 mA at 12 VDC  
EHN- and EC-series models: 1 mA at 12 VDC

Load

With continuous load current.

With load current shut off.

Summary of Contents for G3PX

Page 1: ...and Incorporating Overcurrent Detecting and Single Heater Open Circuit Detecting Functions OMRON s unique design and carefully selected materials made it possible to produce a compact and lightweight...

Page 2: ...X Accessory for G3PX 2 Basic Model Name CT CT Unit 3 Length of Lead Wires 03 30 cm 10 100 cm 4 Series Blank Series for single heater open circuit detection HN Series for multiple heater open circuit d...

Page 3: ...h of the lead wires by adding a code to the model number as shown below G3PX 2 0EC CT03 CT with 30 cm long lead wires G3PX 2 0EC CT10 CT with 100 cm long lead wires 2 When ordering make sure that the...

Page 4: ...2 EHN G32X CT03HN 100 cm G32X CT10HN 30 cm G3PX 2 EC G32X CT03C 100 cm G32X CT10C Name Carry current Applicable models Model Power Device Cartridge 20 A G3PX 220E G32X A20 40 A G3PX 240E G32X A40 60 A...

Page 5: ...ange 0 to 95 Internal duty setting range 0 to 100 10 to 100 See note 1 0 to 100 External duty setting range 0 to 100 10 to 100 See note 1 0 to 100 Start up time See note 2 Approx 0 5 to 10 s See note...

Page 6: ...330 A within 1 cycle Constant current 3 max with 10 time increment of load value 3 max with 10 change of voltage Abnormality detection time 1 s max Voltage drop with output ON 1 6 V max RMS Leakage cu...

Page 7: ...100 60 40 20 G3PX EUN EH EHN Models Output voltage Input current mA G3PX EC Models G3PX EUN EH EHN Models Output voltage Input current mA 100 60 40 20 Output voltage Input current mA G3PX 2 0EUN Model...

Page 8: ...ent A Peak Inrush current A Peak G3PX 220E Models Energized time ms G3PX 240E Models G3PX 260E Models Energized time ms Energized time ms Note The above are possible on condition that the G3PX is in n...

Page 9: ...r Device Cartridge TIME adjuster for extended soft start time DUTY adjuster for internal slope setting ALARM adjuster for multiple heater open circuit detection OPEN indicator for multiple heater open...

Page 10: ...tinue operating with level indication 2 When EH EHN EC series models detect a short mode failure the SHORT indicator is lit and the SPDT relay output is ON Note When the G3PX detects a short mode fail...

Page 11: ...or the G3PX and the load Load 1 Load 2 Load 200 230 VAC 100 110 VAC 1 2 3 4 5 6 7 8 9 10 G3PX 250 4 5 G3PX 4 5 250 G3PX 600 Load 1 Load 2 4 to 20 mA 4 to 20 mA Impedance Note Two G3PX models can be co...

Page 12: ...ications No of G3PX E5 K 40 mA at 12 V 20 sets E5 N 20 mA at 12 V 20 sets 20 mA at 5 V 20 sets 10 mA at 5 V 20 sets 1 2 3 4 5 6 7 8 9 10 3 2 1 G3PX Load 1 Load 2 DUTY Note You can change the duty with...

Page 13: ...OPEN indicator is lit Stop turning the ALARM adjuster as soon as the indicator is lit to complete the setting 3 2 1 G3PX 1 2 3 4 5 6 7 8 9 10 3 2 1 Load 1 Load 2 DUTY G32X V3K or G32X V2K External DU...

Page 14: ...g as the controlled phase is approximately 1 6 or more in width 2 Be sure to prepare terminals 18 and 19 corresponding to the supply frequency of 50 Hz or 60 Hz Otherwise a setting error will result i...

Page 15: ...on the indented portions of the Power Device Cartridge as shown in the illustration below and pull up the Power Device Cartridge vertically Mounting The procedures for mounting the Power Device Cartr...

Page 16: ...nter screws of the G3PX with a tightening torque of 0 59 to 0 78 N m 6 Attach the terminal cover 7 Switch on the power and check the G3PX to be sure it works properly External Variable Resistor The G3...

Page 17: ...6 8 6 140 0 2 50 0 2 130 119 108 120 13 13 109 8 140 0 2 65 0 2 130 140 0 3 50 0 3 7 6 7 6 G3PX 220E Series G3PX 240E Series Mounting Holes Two M4 screws 70 max 130 max 150 max 130 max 65 0 2 85 max...

Page 18: ...0 2 50 30 9 5 24 35 14 55 40 17 G32X CT03 Series G32X CT10 Series Mounting Holes Two 4 5 dia or M4 holes 60 max see note 2 17 dia hole 15 dia see note 1 Note 1 Color of the hole EH Series Black EHN Se...

Page 19: ...input VOLTAGE IN Current input 4 to 20 mA DC CURRENT External duty setting 3 k B MAN DUTY SET 200 230 VAC 50 60 Hz 100 110 VAC 50 60 Hz 2 k B 2 W for EUN series models Internal contact configuration E...

Page 20: ...model 1 47 N m 40 A model 2 45 N m 60 A model 4 12 N m Terminal block Single phase model 0 98 N m Be sure to protect the terminals with the protective cover after wiring Wiring for Error Detection If...

Page 21: ...e Models Only Do not apply 200 V to the 100 V terminals otherwise the thermal fuse of the built in transformer will be blown and the G3PX will not operate Others It is not possible to use three single...

Page 22: ...no power control operation is possible Make sure that the load current is large enough Countermeasure 1 Adjust the CUR LIM adjuster so that the LED on the farthest right of the Level indicator is OFF...

Reviews: