G3PJ

7

Mounting

• The G3PJ is heavy. Firmly mount the DIN Track and secure both 

ends with End Plates for DIN Track mounting models. When 
mounting the G3PJ directly to a panel, firmly secure it to the panel.

Screw diameter: 

M4

Tightening torque: 

0.98 to 1.47 N·m

Note:

Make sure that the load current is 50% of the rated load current 
when the G3PJ is mounted horizontally. 
For details on close mounting, refer to the related information 
under performance characteristics.
Mount the G3PJ in a direction so that the markings read 
naturally.

Wiring

• When using crimp terminals, refer to the terminal clearances 

shown below.

• Make sure that all lead wires are thick enough for the current.
• To isolate the Relay from the power supply, install an appropriate 

circuit breaker between the power supply and the Relay.
Always turn OFF the power supply before wiring the Unit.

Push-in plus technology

1. Connecting Wires to the Push-in plus technology

Part Names of the technology

Connecting Wires with Ferrules and Solid Wires

Insert the solid wire or ferrule straight into the terminal until the end 
strikes the terminal.

If a wire is difficult to connect because it is too thin, use a flat-blade 
screwdriver in the same way as when connecting stranded wire.

Connecting Stranded Wires

Use the following procedure to connect the wires to the terminal.

1.

Hold a flat-blade screwdriver at an angle and insert it into the 
release hole.
The angle should be between 10° and 15°. If the flat-blade 
screwdriver is inserted correctly, you will feel the spring in the 
release hole respond.

2.

With the flat-blade screwdriver still inserted into the release hole, 
insert the wire into the terminal hole until it strikes the terminal.

3.

Remove the flat-blade screwdriver from the release hole.

Checking Connections

• After insertion, pull gently on the wire to make sure that it will not 

come out (i.e., to confirm that it is held by the terminal).

• To prevent short circuits, insert the stripped part of a stranded or 

solid wire or the conductive part of a ferrule until it is hidden inside 
the terminal insertion hole. (See following diagram.)

Panel

Mounted on a

vertical surface

Vertical
Direction

Panel

Mounted on a 

horizontal surface

10 mm

15-A and 25-A Models

Screw Terminals

Push-in Terminals

12.4 mm

M4 (15 A, 25 A)

10 mm

7.0 mm

M3.5

Output Terminal Section

Input Terminal Section

Release hole

Terminal (Insertion) hole

Release hole

Terminal (Insertion) hole

Ferrule

Release hole

Flat-blade screwdriver

1

10 to 15°

Stranded Wires

2

3

Summary of Contents for G3PJ Series

Page 1: ...t have been certified for safety standards refer to your OMRON website Refer to Safety Precautions on page 5 Input terminal Output terminal Insulation method Operation indicator Rated input voltage Ze...

Page 2: ...C 50 60 Hz 75 to 528 VAC 50 60 Hz Close mounting 15 A Separate mounting 23 A 150 A 60 Hz 1 cycle 1 350A2 s G3PJ 525B PU Close mounting 25 A Separate mounting 27 A 220 A 60 Hz 1 cycle 6 600A2 s Model I...

Page 3: ...0 0 20 40 60 80 100 Ambient temperature C Load current A G3PJ 225B PU G3PJ 525B PU G3PJ 215B PU G3PJ 515B PU 30 20 0 20 40 60 80 100 Ambient temperature C 40 30 20 12 10 8 5 0 G3PJ 215B PU G3PJ 515B P...

Page 4: ...c r i c r e g g i r T Input side Input side Output side t i u c r i c r e g g i r T t i u c r i c t u p n I t i u c r i c t u p n I 2 M4 26 5 41 5 4 2 6 1 Note Without terminal cover 68 13 0 2 100 ma...

Page 5: ...during transportation or mounting Doing so may result in deterioration of performance malfunction or failure Operating and Storage Environments Do not use or store the G3PJ in the following locations...

Page 6: ...pull on it with excessive force Doing so may cause the wire disconnection Do not insert more than one wire into each terminal insertion hole To prevent wiring materials from smoking or ignition use t...

Page 7: ...it is too thin use a flat blade screwdriver in the same way as when connecting stranded wire Connecting Stranded Wires Use the following procedure to connect the wires to the terminal 1 Hold a flat bl...

Page 8: ...nnected to the load power supply The input cable must be less than 3 m 2 The G3PJ with Rated Load Voltage of 100 to 480 VAC 5 B model A capacitor must be connected to the input power supply A capacito...

Page 9: ...is measured at an ambient temperature of 40 C The G3PJ uses a semiconductor to switch the load This causes the temperature inside the control panel to increase due to heating resulting from the flow o...

Page 10: ...MEMO 10...

Page 11: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 12: ...L 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron c...

Reviews: