background image

G3PJ

5

Safety Precautions

Be sure to read the 

Safety Precautions for All Solid State Relays

 in the website at the following URL: 

http://www.ia.omron.com/.

Format of Warning Indications

Meaning of Graphic Symbols for Ensuring Product Safety

Minor electrical shock may occasionally occur.
Do not touch the G3PJ terminal section (i.e., current-
carrying parts) while the power is being supplied. 
Also, always attach the cover terminal.

The G3PJ may rupture if short-circuit current flows. As 
protection against accidents due to short-circuiting, 
be sure to install protective devices, such as fuses 
and no-fuse breakers, on the power supply side.

Minor electrical shock may occasionally occur.
Do not touch the main circuit terminals on the G3PJ 
immediately after the power supply has been turned 
OFF. Shock may result due to the electrical charge 
stored in the built-in snubber circuit.

Minor burns may occasionally occur. 
Do not touch the G3PJ or the heat sink while the 
power is being supplied or immediately after the 
power supply has been turned OFF. The G3PJ and 
heat sink become extremely hot.

OMRON constantly strives to improve quality and reliability.
The G3PJ, however, use semiconductors, and semiconductors may 
commonly malfunction or fail. In particular, it may not be possible to 
ensure safety if the G3PJ are used outside the rated ranges.
Therefore, always use the SSRs within the ratings. When using the 
G3PJ, always design the system to ensure safety and prevent human 
accidents, fires, and social harm in the event of the G3PJ failure. 
System design must include measures such as system redundancy, 
measures to prevent fires from spreading, and designs to prevent 
malfunction.

Transport

Do not transport the G3PJ under the following conditions.
Doing so may result in damage, malfunction, or deterioration of 
performance characteristics.

• Conditions in which the G3PJ may be subject to water.
• Conditions in which the G3PJ may be subject to high temperature 

or high humidity.

• Conditions in which the G3PJ is not packaged.
• Do not drop the G3PJ or subject it to abnormal vibration or shock 

during transportation or mounting. Doing so may result in 
deterioration of performance, malfunction, or failure.

Operating and Storage Environments

Do not use or store the G3PJ in the following locations. Doing so may 
result in damage, malfunction, or deterioration of performance 
characteristics.

• Locations subject to rainwater or water splashes.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to high temperature or high humidity.
• Do not store in locations subject to ambient storage temperatures 

outside the range 

30 to 100

C. 

• Locations subject to relative humidity outside the range 35% to 

85% or locations in which condensation may occur due to rapid 
changes in temperature.

• Locations subject to corrosive gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to direct sunlight.
• Locations subject to shock or vibration.
• Do not allow solvents such as thinners or gasoline to come into 

contact with the plastic parts of the G3PJ. A solvent may erase the 
markings.

• Do not allow oil to come into contact with the terminal cover on the 

G3PJ. The cover may become milky or crack.

Installation and Handling

• Do not block the movement of the air surrounding the G3PJ or heat 

sink. Abnormal heating of the G3PJ may result in shorting failures 
of the output elements or burn damage. 

• Do not use the G3PJ if the heat radiation fins have been bent by 

being dropped. Doing so may result in malfunction due to a 
reduction in the heat radiation performance. 

• Do not handle the G3PJ with oily or dusty (especially iron dust) 

hands. Doing so may result in malfunction.

CAUTION

Indicates a potentially hazardous situation 
which, if not avoided, may result in minor or 
moderate injury or in property damage.

Precautions for 

Safe Use

Indicates supplementary comments on 
what to do or avoid doing, to use the 
product safety.

Precautions for 

Correct Use

Includes operating precautions to ensure 
that the product will operate properly and 
that performance and functions will not be 
adversely affected.

Indicates the possibility of electric shock under 
specific conditions.

Indicates the possibility of explosion under specific 
conditions.

Indicates the possibility of injuries by high 
temperature under specific conditions.

 

CAUTION

Precautions for Safe Use

Summary of Contents for G3PJ Series

Page 1: ...t have been certified for safety standards refer to your OMRON website Refer to Safety Precautions on page 5 Input terminal Output terminal Insulation method Operation indicator Rated input voltage Ze...

Page 2: ...C 50 60 Hz 75 to 528 VAC 50 60 Hz Close mounting 15 A Separate mounting 23 A 150 A 60 Hz 1 cycle 1 350A2 s G3PJ 525B PU Close mounting 25 A Separate mounting 27 A 220 A 60 Hz 1 cycle 6 600A2 s Model I...

Page 3: ...0 0 20 40 60 80 100 Ambient temperature C Load current A G3PJ 225B PU G3PJ 525B PU G3PJ 215B PU G3PJ 515B PU 30 20 0 20 40 60 80 100 Ambient temperature C 40 30 20 12 10 8 5 0 G3PJ 215B PU G3PJ 515B P...

Page 4: ...c r i c r e g g i r T Input side Input side Output side t i u c r i c r e g g i r T t i u c r i c t u p n I t i u c r i c t u p n I 2 M4 26 5 41 5 4 2 6 1 Note Without terminal cover 68 13 0 2 100 ma...

Page 5: ...during transportation or mounting Doing so may result in deterioration of performance malfunction or failure Operating and Storage Environments Do not use or store the G3PJ in the following locations...

Page 6: ...pull on it with excessive force Doing so may cause the wire disconnection Do not insert more than one wire into each terminal insertion hole To prevent wiring materials from smoking or ignition use t...

Page 7: ...it is too thin use a flat blade screwdriver in the same way as when connecting stranded wire Connecting Stranded Wires Use the following procedure to connect the wires to the terminal 1 Hold a flat bl...

Page 8: ...nnected to the load power supply The input cable must be less than 3 m 2 The G3PJ with Rated Load Voltage of 100 to 480 VAC 5 B model A capacitor must be connected to the input power supply A capacito...

Page 9: ...is measured at an ambient temperature of 40 C The G3PJ uses a semiconductor to switch the load This causes the temperature inside the control panel to increase due to heating resulting from the flow o...

Page 10: ...MEMO 10...

Page 11: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 12: ...L 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron c...