20
Section 7: Muting and override functions
Where:
D: minimum dimension of package that can cross the SLC.
D1:
distance between muting actuator B and SLC.
It MUST be as short as possible.
Minimum distance allowable depends on the speed of conveyour, the response time of SLC and
response time of muting actuator.
D2:
Distance between muting actuator A and muting actuator B.
It must be > 250mm
It also depends on the conveyour speed:
d
max
[cm] = v[m/s] * 3[s] * 100 > 25
It is necessary that this distance does not allow both sensors to be activated and thus muting if a person
goes through by accident.
•
The TEST/RESTART button must be located so that the operator can see the protected area when
restarting, testing or overriding.
•
The external illuminated indicator for muting override enabled must be located so that it can be seen
from all sides of operation.
•
If the muting sensors are installed very close to the SLC, care must be taken that the receivers of the
sensors are mounted on the mirror side of the SLC in order to avoid interference.
•
The system is protected against the possibility of faults due to damage to the wires; however we recom-
mend laying the cables for all connections in order to avoid damage to the connection cables.
Supply Cable
Muting cable
RX cable
TX cable
Muting
lamp
Start & Test
buttons
Protect
cables
Cable to lamp