![background image](http://html1.mh-extra.com/html/omron/f3em2-series/f3em2-series_operation-manual_741281028.webp)
5-2
5-1 DIP switch setting - Overview
F3EM2 MEASURING LIGHT CURTAINS OPERATION MANUAL
5
Operating serial
output models
The RS-232C serial interface of F3EM is specified as follows:
• Full duplex operation
• Data format: 8-N-1 (bit start - 8-bit data - 1-bit stop - no parity)
• The signal on analogue output is calculated as shown in chapter 4-2 ’Analog output value’
5-1 DIP switch setting - Overview
Dip switch setting transmitter:
Dip-SW
Status
Function
1
OFF
Optical Synch (default)
ON
Wire synch
2+3
RS baud rate
2
3
Speed
OFF
OFF
9600bps (default)
OFF
ON
19200bps
ON
OFF
38400bps
ON
ON
76800bps
4
Not used
5
OFF
FAR (default)
ON
NEAR
6+7+8
Output function
6
7
8
Serial output
Analogue output
OFF
OFF
OFF
Bitmap of optics (default) NAB
(default)
OFF
OFF
ON
FBB + NBB (4 byte total)
NAB
OFF
ON
OFF
FBM + NAB (4 byte total)
LBB
OFF
ON
ON
LBB + NBB (4 byte total)
NBB
ON
OFF
OFF
LBM + NAB (4 byte total)
FBB
ON
OFF
ON
Continuous bitmap
transmission
disabled
ON
ON
OFF
FBB + LBB (4 byte total)
NBB
ON
ON
ON
Holes detection
disabled
Summary of Contents for F3EM2 Series
Page 4: ......
Page 6: ...4...
Page 10: ......
Page 18: ......
Page 22: ......
Page 26: ......
Page 35: ...F3EM2 MEASURING LIGHT CURTAINS OPERATION MANUAL 6 Order codes...
Page 37: ...F3EM2 MEASURING LIGHT CURTAINS OPERATION MANUAL 7 7 1 Ratings 7 2 Technical specifications...
Page 43: ...F3EM2 MEASURING LIGHT CURTAINS OPERATION MANUAL 9 Dimensions...