2-3
Section
Setting Selectors and Switch
14
Pin 5 is used to set the startup operation.
Startup operation
Stop operation control
Continue status at
power OFF
Pin 5
The factory setting is for stop operation control (pin 5 OFF).
If the power is turned OFF during manual operation and pin 5 is set to ON (con-
tinuous operation), manual operation will automatically begin when the power is
turned ON again. The output value will be 0%.
Pin 6 is used to set the unit for measuring temperature.
Temperature unit
C
F
Pin 6
The factory setting is for degrees Celsius (pin 6 OFF).
When the temperature unit is changed, the temperature data does not automati-
cally change, so make sure to reset the temperature using the following proce-
dure.
1, 2, 3...
1. Initialize the setting data.
2. Recalculate the data according to the following conversion formula and re-
set the control data within the setting range.
(value in
F) = 1.8 x (value in
C) + 32
3. Store the settings in memory.
Pins 3, 4, 5, and 8 are used to change the operation mode.
E5ZE operation mode
Control mode
Hardware test mode
Pins 3, 4, 5, and 8
The factory setting is for Control Mode (pins 3, 4, 5, and 8 all OFF).
Control Mode:
Use for normal temperature control.
Hardware Test Mode:
Use for testing Peripheral Devices and wiring.
Refer to Appendix E for details on how to use Hardware Test Mode. Outputs can
be turned ON and OFF in Hardware Test Mode regardless of the process value.
Startup Operation
Temperature Unit
Operation Mode Change