78
End Codes
If an end code of 00 was returned in the response, the command was executed
normally. If the end code is not 00, the desired data will not have been written.
Refer to
Section 4-1-2 End Codes
for a description of the other possible end
codes and their meanings.
4-2-5
Reading PID Constant and the Control Period
This section covers four commands: Proportional Band Read, Integral Time
Read, Derivative Time Read, and Control Period Read. The command and re-
sponse formats for these are nearly the same. The numeric values returned for
data do vary.
Note
The following commands can not used during autotuning.
Command Format
The formats for all of these commands require the unit number, control point,
and memory bank for which the read is intended.
Proportional Band Read: RB
@
0
Unit R
B
Bank Point
0
0
CR
Header code
*
Data code
Terminator
FCS
Integral Time Read: RN
@
0
Unit R
N
Bank Point
0
0
CR
Header code
FCS
*
Data code
Terminator
FCS
Derivative Time Read: RV
@
0
Unit R
V
Bank Point
0
0
CR
Header code
FCS
FCS
*
Data code
Terminator
Control Period Read: RT
@
0
Unit R
T
Bank Point
0
0
CR
Header code
FCS
FCS
*
Data code
Terminator
Command Examples
The following command is used to read the proportional band in memory bank 3
for control point 2 of unit 1.
@ 0
1
R
B
3
2
0
0
5
0
CR
*
Temperature Control Commands (All Controllers)
Section 4-2
Summary of Contents for E5ZD
Page 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Page 2: ......
Page 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 8: ......
Page 10: ......
Page 18: ......
Page 76: ......
Page 128: ......
Page 132: ......
Page 142: ......
Page 146: ......
Page 148: ......
Page 150: ......
Page 154: ......
Page 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...