121
Command:
@ 0 0 R X 0 0 0 0 FCS * CR
Response:
@ 0 0 R X 0 0 0 1 0 0 FCS * CR
The command includes a total of 13 characters (FCS would be two; CR, one)
and the response includes 15. Placing 13 and 15 into the above equation pro-
duces the following:
(13 characters x 11 bits/character)/9.6 bits/ms + 50 ms + 500 ms =
570 ms (approximate) + (15 characters x 11 bits/character)/9.6 bits/ms
= 13 x 11/9.6 + 50 + 500 + 15 x 11/9.6 ms
= 583 ms (approximate)
13
characters
11
bits per character
9.6
bits
[
15
ms
15
characters
11
bits per character
9.6
bits
[
18
ms
50
ms
)
500
ms
)
18
ms
+
568
ms
Command:
Response:
Fuzzy-logic Controllers:
Other Controllers:
150
ms
)
500
ms
)
18
ms
+
668
ms
The measured temperature would thus be returned to the host computer a maxi-
mum of 683 ms (15 ms + 668 ms) or 583 ms (15 ms + 568 ms) after the host
computer started transmitting the read command. The measured temperature
that was returned would be the one that was current 668 ms or 568 ms before
the response was received.
Reading Times
Section 5-2
Summary of Contents for E5ZD
Page 1: ...Cat No Z042 E1 4 Multipoint Temperature Controller E5ZD ...
Page 2: ......
Page 3: ...E5ZD Multipoint Temperature Controller Operation Manual Revised November 1996 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 8: ......
Page 10: ......
Page 18: ......
Page 76: ......
Page 128: ......
Page 132: ......
Page 142: ......
Page 146: ......
Page 148: ......
Page 150: ......
Page 154: ......
Page 157: ...Cat No Z042 E1 4 E5ZD Multipoint Temperature Controller OPERATION MANUAL ...